Table 3:
Parameter
Electrostatic discharge
- Electromagnetic field
Fast transients (burst)
Voltage surges - DC supply connection
Voltage surges - data line
Conducted disturbances
Damped oscillation - DC supply connection EN 61000-4-12 IEEE C37.90.1 line/ground 2.5 kV
Damped oscillation - data line
Table 4:
Parameter
Vibration
Shock
Table 5:
Parameter
Rated voltage
Voltage range including maximum toler-
ances
Connection type
Power loss buffer
Back-up fuse for each voltage input
2019-04-30
EMC (continued)
Stability
Interface Power Supply High Voltage
Specification
EN 61000-4-2 IEEE C37.90.3
Contact discharge ±8 kV
EN 61000-4-2 IEEE C37.90.3
Air discharge ±15 kV
EN 61000-4-3 80 MHz ..3000 MHz
max. 10 V/m
IEEE 1613 80 MHz ...1000 MHz
35 V/m
EN 61000-4-4 IEEE C37.90.1 DC supply connection
±4 kV
EN 61000-4-4 IEEE C37.90.1
Data line ±4 kV
EN 61000-4-5 line/ground ±2 kV
IEEE 1613 line/ground ±5 kV
EN 61000-4-5 line/line ±1 kV
EN 61000-4-5 line/ground ±2 kV
EN 61000-4-6 150 kHz ... 80 MHz 10 V
EN 61000-4-12 IEEE C37.90.1 line/line 1 kV
EN 61000-4-12 IEEE C37.90.1 line/ground 2.5 kV
EN 61000-4-12 line/line ±1 kV
Specification
IEC 60068-2-6, test Fc
2 Hz ... 9 Hz with 3 mm (0.11 in) amplitude 9 Hz ... 200 Hz
with 1 g
200 Hz ...500 Hz with 1.5g
IEC 60068-2-27, test Ea
10 g at 11 ms
Specification
110 V AC ... 240 V AC, 50 Hz ... 60 Hz
110 V DC ... 250 V DC
88 V AC ... 276 V AC
88 V DC ... 288 V DC
3-pin terminal block
Tightening torque 0.5 Nm (4.4 lb-in)
min. conductor diameter
Supply with AC voltage: AWG18 (0.75 mm²)
Supply with DC voltage: AWG16 (1 mm²)
max. conductor diameter: AWG12 (2.5 mm²)
>20 ms at 230 V DC
Nominal rating: 2.5 A
Characteristic: slow blow
EQUIPMENT SPECIFICATION