Siemens GEAFOL Neo Operating Manual page 22

Cast-resin dry type distribution transformer
Table of Contents

Advertisement

7. Commissioning
7.3 Pre-commissioning test
7.3.1 Voltage ratio test: Measure the voltage ratio of the winding under all taps and the connection group. The
allowable deviation of rated tap voltage ratio shall not exceed ± 0.5%, except for special transformers.
7.3.2 Wingding resistance test: Measure the DC resistance of the winding at all taps and records the winding
temperature.
7.3.3 Insulation resistance test: Measure the insulation resistance values of the windings and cores (as shown in the
table below) and record ambient temperature and humidity.
Typically, the insulation resistance is measured at ambient temperature of-25 º C ~ 50 º C, humidity ≤ 90%, and
the insulation resistance of the transformer would decrease in humid environment. If the transformer suffers from
dampness, the transformer can be dried. If the insulation resistance is not less than 2 MΩ, a voltage can be applied to
the low-voltage side of the transformer and the transformer can be dried by no-load heating. If the insulation resistance
value is less than 2 MΩ, it can be dried by air drying or baking with heat lamp.
Test position
High voltage terminal -
low voltage terminal + ground
Low voltage terminal -
High voltage terminal + ground
High voltage terminal + low voltage terminal
- ground
Iron core - ground
Note:
• After testing the insulation resistance of the iron core-ground, it is necessary to restore the connection of the grounding strap.
7.3.4 Applied withstand voltage test: The withstand voltage strength of the transformer is tested. The on-site tested
withstand voltage value is 80% of the factory test voltage value. The factory test withstand voltage value can be
shown in the factory test report and nameplate.
20
Test equipment
2500 V Megohmmeter
2500 V Megohmmeter
2500 V Megohmmeter
2500 V Megohmmeter
Test value requirements
≥100 MΩ
≥100 MΩ
≥100 MΩ
≥10 MΩ