Figure 3-18
Installation openings for the power unit with external air cooling, 300 mm
Table 3-19
Dimensions of the installation openings for the power unit with external air cooling
Component width
50 mm
100 mm
150 mm
200 mm
300 mm
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
W [mm] (inches)
41.5 + 0.3 (1.63 + 0.012)
89.5 + 0.3 (3.52 + 0.012)
133 + 0.3 (5.24 + 0.012)
173 + 0.3 (6.81 + 0.012)
278 + 0.3 (10.94 + 0.012)
3.3 Active Line Modules with External Air Cooling
w1 [mm] (inches)
20.75 +0.15 (0.82 +0.006)
19.75 +0.15 (0.78 + 0.006)
16.5 +0.15 (0.65 + 0.006)
11.5 +0.15 (0.45 + 0.006)
14.0 ± 0.15 (0.55 ± 0.006)
Line Modules Booksize
w2 [mm] (inches)
0
50 ± 0.15 (1.97 ± 0.006)
100 ± 0.15 (3.94 ± 0.006)
150 ± 0.15 (5.91 ± 0.006)
250 + 0.15 (9.84 + 0.006)