5.3 WIRING RECOMMENDATION—ERGONOMIC UNIVERSAL STATION
The ergonomic Universal Station is designed to accommodate conduit access from the rear
of the station or from beneath the floor.
•
Figure 5-3 shows access from the rear of the station.
•
Figure 5-4 shows access from beneath the station.
•
Figure 5-5 show the interior of the connection box.
Wiring entry to an ergonomic Universal Station can be made from the rear or through the
1 1/2" hole in the cabinet. The following conduit parts were used in the design of the
access.
Table 5-1 — Conduit Parts for Installation of an Ergonomic Universal Station
Function
3/4" 90° Pulling Elbow Male to Female
3/4" Zinc Die Cast Screw-in Connector with Steel
Locknut
3/4" Clamp Connector for Onmetallic Sheathed and
Flexible Wire
Wiring should be AWG 14-3/2.5 mm 2 or larger for greater cable lengths. See TPS
•
System Site Planning.
SERVICE
120 Vac
240 Vac
LCN System Installation
BREAKER SIZE
15 Amp
15 Amp
5-3
Source
Appleton
Bridgeport
Midwest/Cooper
O-Z/Gadney
RACO
Appleton
Bridgeport
Midwest/Cooper
O-Z/Gadney
RACO
Honeywell
5.3
Part Number
MFL-75
72-DC
811
MF-075
2663
SGC-75DC
521-DC
772
51190714