Configuration; Tolerance Of Power Operated Shutdown - Baier PROMETHEUS Series Instruction Manual

24v motor control device for flush box mounting
Table of Contents

Advertisement

Initial operation

6.1 Configuration

Overtightened potentiometer
Damage of control device may result in malfunction.
Potentiometers have a right and a left stop, which must not
be overtightened.
 Adjust potentiometer only with low force and with an
appropriate screw driver.
Hint
Changes in configuration when the initial operation is done, will force
the control device to perform a new initial operation.
 Perform initial operation, refer to chapter 6.2

6.1.1 Tolerance of power operated shutdown

In some cases the drive will not shut down correctly during or after initial operation.
Or the drive stops, before it has reached the end position. This particularly happens,
when a very heavy or a very lightweight wing is used.
Motor overload
Damage of components by motor overload.
 Check after any change of configuration, if the control
device shuts down correctly.
 Do not set tolerance too high.
When the drive stops early
 Turn potentiometer 1 clockwise
 Drive switches off later
When the drive does not stop
 Turn potentiometer 1 counterclockwise
 Drive switches off sooner
Hint
After a maximum time of 5 minutes, the drive switches off in each case.
24V motor control device for flush box mounting - Version 1.1
w w w . b a i e r - g m b h . d e
N O T I C E
N O T I C E
6
Increase tolerance
Decrease tolerance
13/22