High level alarm test with reference reflector

Prior to running a proof test you will have to ensure that a Proof Test Reference Reflector is
installed and properly calibrated and configured
appropriate level below the Proof Test Reference Reflector. A Reference Reflector can be
used with the Rosemount 5900 Parabolic and Array antennas.
See the Rosemount 5900 Proof Test
and configure a proof test Reference Reflector.
The High Alarm Test must be combined with suitable output verification test such as Analog
Output or Relays K1/K2.
To run a proof test for a Rosemount 5900 with Reference Reflector do the following:
1.
2.
Note
The reference reflector must be configured
enabled.
3.
4.
5.
1.
See the Rosemount 5900 Proof Test
Operation and Maintenance
Ensure that the TankMaster WinSetup program is up and running.
In the WinSetup workspace, click the right mouse button on the Rosemount 5900
device icon and select the Proof Test option. The Proof Test window appears.
Select the Reference Reflector check box (see
Select one of the check boxes depending on the output option that is used:
Analog Output, or
Relays K1/K2 verification tests
Click the Start Guided Proof Test button to open the High Level Alarm Test window:
Manual Supplement
for more information.
Operation and Maintenance
(1)
. Ensure that High Alarm is set to an
Manual Supplement
for instructions on how to install
(1)
for the Guided Proof Test function to be
"Maintenance" on page
November 2019
29).
19