Relay Configuration - Emerson Rosemount 5900 Safety Manual

Radar level gauge and tank hub
Table of Contents

Advertisement

Safety Manual
00809-0400-5100, Rev AB
2.3.2

Relay configuration

To configure Rosemount 2410 Tank Hub relays:
1.
2.
Normally Open/Normally Closed
Normally Open (NO) is the default setting for the Rosemount 5900 and Rosemount 2410 in
Safety Instrumented Systems (SIS). Verify the relay configuration by, for example, using the
proof test function Relays K1/K2 Verification Test. See
information.
See the Rosemount 2410 Tank Hub
Rosemount 2410 relays.
Note
In case a Proof Test Reference Reflector is used, make sure that the relay set point is set
below the position of the reflector.
1.
Document No 00809-0100-2410
Installation and Configuration
In the WinSetup workspace click the right mouse button on the tank hub icon,
choose Properties and select the Configuration tab.
Click one of the Virtual Relay No. buttons. See Appendix C in the Rosemount 2410
Tank Hub
Reference Manual
Installation and Configuration
(1)
for more information on how to configure relays.
"Maintenance" on page 29
(1)
Reference Manual
for more information on the
November 2019
for more
11