Procedure 5-1: Connect ground cable

Purpose
Follow this procedure to connect the ground cable to the Alcatel-Lucent 9764 Compact
Metro Cell Outdoor.
Before you begin
Ensure the following:
 All site preparation activities for cabling have been completed.
 All installation procedures for the 9764 CMCO have been completed.
Steps
Note: The 9764 CMCO must be grounded with a 16 mm
NYY-1x16 mm
The grounding cable is not included in the delivery and must be locally supplied.
To attach the ground cable perform the following steps:
...................................................................................................................................................................................................
Route the ground cable from the ground system to the 9764 CMCO.
1
...................................................................................................................................................................................................
At the 9764 CMCO, cut the cable to a proper length, strip the cable end and crimp a
2
2-hole ground lug, with holes suitable for M6 screws, on the end of the cable.
Clean the contact surface area and use antioxidant to avoid oxidation.
...................................................................................................................................................................................................
Connect the ground lug to the grounding point on the 9764 CMCO using the supplied M6
3
screws, lock washers, and flat washers. Use antioxidant at the grounding pads.
...................................................................................................................................................................................................................................
2
or similar) to a grounding system.
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements