Installation of the 9764 Metro Dock
9764 Metro Dock cabling
....................................................................................................................................................................................................................................

Procedure 7-5: 9764 Metro Dock ground cabling

Purpose
This topic describes the procedures to be followed when connecting the grounding cable
to the 9764 Metro Dock.
Important! The following must be observed:
• This equipment must be externally grounded to an appropriate grounding system
using Yellow/Green 10 mm
from Alcatel-Lucent or be locally supplied.
• All grounding system material (cable, connectors, etc.) must be of high quality, that
resist deterioration and require little or no maintenance.
• Installation of the equipment must comply with local and national electrical codes and
guidelines. If there is uncertainty that suitable grounding is available contact the
appropriate site preparation contact or electrical inspection authority.
Connect the ground cable
To attach the ground cable to the 9764 Metro Dock perform the following steps.
...................................................................................................................................................................................................
Route the ground cable from the site grounding system to the 9764 Metro Dock.
1
...................................................................................................................................................................................................
2
At the 9764 Metro Dock cut the ground cable to a proper length and strip the cable end to
expose approximately 20 mm (0.75 in).
...................................................................................................................................................................................................
Place a double hole cable lug (with a holes suitable for M6 screws) onto the end of the
3
cable. Using an appropriate crimping tool, crimp the lug onto the cable.
...................................................................................................................................................................................................
Clean the contact surface area of the cable lug and earthing point on the 9764 Metro Dock
4
and use antioxidant to avoid oxidation.
....................................................................................................................................................................................................................................