Honeywell Ex-Or CDW12U5 Installation And Commissioning Instructions page 3

Mls connect digital plug-in programmable lighting control module

Advertisement

Commissioning
The CDW12U5 can be commissioned using the QuickSet Pro hand-held programmer or from a dedicated programme running on a portable PC. Communication from the PC can be by
means of a USB Infrared Transceiver which can signal directly to the CDW12U5's onboard infrared port over a short range or via any attached detector over longer ranges. Alternatively a
specialised wired serial link can be established with the CDW12U5 itself. The main parameters available for configuration are shown below. Parameters may be re-programmed any
number of times and all settings will be retained in the event of a power loss.
PARAMETERS
Per Box Parameters:
Switches 1A-5B & 6A-7B (RF1 & 2): Mode
Detector 1-5: Range (On & Off Sensitivity)
Detector 1-5: Sensitivity Fine
Common: Address
Common: Switch Map
Common: LED Inhibit
Common: Inhibit DALI Init
Common: Missing Detector
Common: Slow Dim (mins)
Common: Bus Absent All On
Per Channel Parameters:
Assigned Detectors
Pcell Source
Assigned Switches
Power Up
Occ Trigger Mode
Low Lux Level (Auto Absence)
Sw Auto Detect
Manual I/P
Occupied Scene
Alt. Occ. Scene A & B
Start Lamps
Occupied Timer
Photocell
Bright Out
Set-Point Low / High
Scene 2-6
Transition Scene
Transition Timer
Background Level
Alt. Background Scene A & B
Background Tmr
Fade to Off
Bus Connect
Zones 1-4
Zones 1-4 TRX
Corridor 1-2: Begin / End
Corridor Scene
Global 1-2 Rx
Ballast
Lamp Max
Burn-In Hrs
Quick Burn-In
Burn-In Dimming
Offset Dimming
SELV Switch Options
Sustain
Brighten
Dim
Off
Scene 1-6
On
Partition
OneSwitch
On-Dim
Off-Brighten
On / Brighten
Off / Dim
Emergency Tst
Emergency End
Last Out
Door Open / Door Closed
Keycard In / Keycard Out
Edge: On, Off, Scene 1-6
Edge: Brighten / Dim
Last Out-On
Time of Day A & B
Unoccupied 10%
Partition Open / Closed
Slow Brighten / Dim
OPTIONS (Defaults, where applicable, shown in bold)
User may choose any option for Switch A or Switch B (see section at end of table for details of SELV switch options).
Max: 100%, 75% or 50% / High: 100%, 75% or 50% / Med: 100%, 75% or 50% / Low: 100%, 75% or 50% / Min: 100% or 75%
Mode A, Mode B or Mode C - Applies when Sensitivity is set to Max and during occupancy only (Mode A = Normal, B & C = More Sensitive)
0-127 - MLS address for DALI Emergency test. Default = 0
Normal / Direct / Direct 2 / Zero Off Dly / Modes 04-07 (for future use) - Pre-set switch mappings (except Zero Off Dly - instant off option)
Yes / No - Enab les or disab les the detector's LEDs.
Yes / No - Prevents the DALI b allasts from b eing initialised every time the b ox powers up.
Normal / On Full - Puts all outputs on if there's a detector assigned to a channel and that detector isn't present.
0-254 - Fade time setting, for use with Slow Dim and Slow Brighten switch functions. Default = 0
Yes / No - All lights default to ON in the event of a b us failure.
Detector 1 - Detector 5 Assigned or Not Assigned to this Channel.
None (--), 1,2,3,4,5 - Photocell 1-5 (in Detectors 1-5) Assigned or Not Assigned to this channel.
Switch 1A - Switch 5B & Switch 6A - 7B (RF) Assigned or Not Assigned to this channel.
On / Off
Presence / Absence / Manual
0-254 (0 = feature disabled) - Used in manual modes: When it is dark, lights respond to movement automatically without requiring switch press.
Yes / No - Used in manual modes: If set to Yes, presence detection is automatic until a switch press is detected.
Local / Share (Local = Ob ey locally only; Share = Ob ey locally and trasmit command on MLS b us)
Scene 1-6 Scene1
Scene 1-6 or -- (feature disabled) - Determines different actions on entry dependent on time of day.
Max / Min
10 seconds to 96 hours, Disabled. 20 mins
Regulate (100%, 90%, 80%, 70%, 60%, 50%) / Passive / Active / Disabled
Yes / No
Photocell Lower and Upper Thresholds: 0-1023 (used in Regulating Scene 1). Low = 350; High = 450
Output 0-100% or -- (no change) Scene 2 = 80%; 3 = 40%; 4 = 20%; 5 = 10%; 6 = 5%
Scene 1-6 or -- (feature disabled) - Scene interposed b etween 'Occ Timer' & 'Background Level' to allow movement to restore lights at existing level.
10 seconds to 96 hours - Determines length of transition scene. 10 secs
Off
Minimum, 25% or Scene 6 (these options show XTN suffix) for 3 x Occupied Timer, then Off.
Minimum, 25% or Scene 6, 5, 4, 3 or 2 (these options show BLD suffix) until the building has been vacated.
Minimum, 25% or Scene 6, 5, 4, 3 or 2 (Background Timer parameter applies to these options which have no suffix).
Scene 1-6 or -- (no scene) - Determines different actions when the area is vacant dependent on time of day.
10 seconds to 96 hours or -- (none) - Applies to 'Alt Exit Scenes' and some 'Background Level' scenes (i.e. not XTN and BLD options). When Background Timer
expires, channel's output turns off.
Yes / No
Yes / No
None (--), Zone number 1-100 / Common 1,2,3
Tx Rx / Tx Only / Rx Only - Determines how zone parameters 1-4 b ehave with respect to b us commands.
None (--), Zone number 1-100 / Bld
Scene 1-6 or -- (no scene) - Movement within an area's Corridor Begin/End span will cause that area to go to the chosen scene. Direct movement within zones 1-4
will override this and the channel will go to its Entry Scene.
Yes / No
1% DSI, 3% DSI, 10% DSI, 1% DALI, 3% DALI, 10% DALI (Non-Dimming - use default i.e. 1% DSI)
100%, 90%, 80%, 70%, 50%, 45%, 40%, 35%, 30%, 25%, 20%, 15%, 10%
Burn-in 100 hrs / Cancel / Resume (See Application Note AN4028 - limited functionality via QuickSet Pro)
Yes / No - If set to Yes, output remains on until 100-hr b urn-in is completed.
Yes / No - If set to Yes, allows temporary (30 secs) dimming in response to manual inputs, even though in 100-hr b urn-in mode.
None (--) to 100% in 10% increments. Allows selected channels to b e configured to b e b righter than a reference channel according to chosen 'output weightings'
(e.g. Ref Ch = 0% (window row), Ch2 = 10% b righter (adjacent to window row), Ch3 = 30% b righter (furthest from windows) - all would work together to achieve
chosen lux level, maintaining respective percentage differences in output).
Description
Imitates movement seen, as a result output of Channel remains ON till the assigned switch with 'SUSTAIN' is active.
Raises the light level. Works only with dimmable ballasts.
Lowers the light level. Works only with dimmable ballasts.
Turns lamp OFF.
Recalls Scene assigned (any Scene 1 to 6 as configured).
Turns lamp ON.
Initiates logical partition of a room. Refer to Application Notes AN4002 & AN4004 for more details.
Simple momentary push-to-make wallswitch that can be used to raise or lower the lighting level or toggle the output of the unit ON or OFF. Short press toggles
output level between ON & OFF, long press will ramp the light level Up or Down.
Short Press will turn the output ON, long press will lower the light level.
Short Press will turn the output OFF, long press will raise the light level.
Short Press will turn the output ON, long press will raise the light level.
Short Press will turn the output OFF, long press will lower the light level.
Imitates manual test of emergency luminaire by turning OFF the Maintained Live.
Restores Maintained Live to end the Emergency Test.
"Last man out" switch, reduces the Occupied Timer to 10 seconds for a fast time-out when leaving the building.
Connected to switches detecting whether door is open or closed. Choice depends on type of operation (normally contact would be closed when door is closed).
Connected to switches detecting whether keycard is inserted or not. Choice depends on type of operation.
Edge-triggered commands as above - sent only once as the switch is pressed.
Each press increments or decrements the DALI output.
Short press = fast time-out for "last man out"; Long press = turns on at Entry Scene for "first man in".
Cause the channels to use Alt. Occupied Scenes A or B and Alt. Background Scenes A or B.
Sends a 'Time Out Now, Go to DALI 10%' message on the MLS bus.
Initiates logical partition of a room - for use with EnOcean reed switch transmitters.
Switch input held causes slow ramp / slow fade. Fade time adjustable in Common menu, 1 min to 254 mins.