Advanced Settings
Heating & Cooling
To access the Heating and Cooling, click Advanced Settings, and enter the Professional Access Code
u
Click on a setting and use the scroll wheel to modify the default value. From this menu you can adjust:
u
TITLE
Default
Fan Delay On
15 Seconds
Fan Delay On Elec
0 Seconds
Fan Delay Off
60 Seconds
Min. Run Time
5 Minutes
Anti Short Cycle
5 Minutes
Cycle Time
180 Seconds
Zero Energy
1° F/ 0.5° C
Band Heating
Zero Energy
1° F/ 0.5° C
Band Cooling
Max
Min
Description
The fan's lag time after the heating or cooling call is initiated when in Fossil Fuel,
120 Seconds
0 Seconds
Heat Pump, or Cooling operation.
The fan's lag time after the heating or cooling call is initiated when in Electric,
5 Seconds
0 Seconds
Auxiliary, or Emergency operation.
120 Seconds
30 Seconds
The fan's lag time after the heating or cooling call is terminated.
Stage Delay
3 Minutes
The minimum amount of time the system will cycle upon engagement.
The Anti Short Cycle (ASC) timer represents the minimum amount of time the
5 Minutes
0 Minutes
system will remain off upon stage down engagement.
300 Seconds
60 Seconds
Time delay between active heating and cooling transition
A temperature range between the current temperature and the heating set point,
2° F/ 1° C
0.5° F/ 0.3° C
where heating is not engaged (also called deadband).
A temperature range between the current temperature and the cooling set point,
2° F/ 1° C
0.5° F/ 0.3° C
where cooling is not engaged (also called deadband).