Step 4-8 Performing Final Checks And Trial Operation - Samsung AR TXHZ Series Installation Manual

Hide thumbs Also See for AR TXHZ Series:
Table of Contents

Advertisement

Installation Inspection and Testing
Error indicator
Display
Communication error between
indoor and outdoor units
Error on indoor temperature sensor
,
Error on indoor heat exchanger
Error on indoor fan motor
,
EEPROM/Option error
,
Refrigerant flow blocking error
Lack of refrigerant (for inverter
models only)
Step 4-8 Performing final checks and
trial operation
WARNING
Stop the unit, disconnect the power, and contact Samsung
technical support if any of the following occurs:
The unit produces a burning smell or smoke.
The power cable is hot or damaged.
The unit is very noisy.
Any foreign substance, such as water, has entered the
appliance.
The appliance becomes flooded.
28
English
Error
Check the cables between the indoor and outdoor units.
See if the power cable or communication cable is crossed.
Make sure that the indoor temperature sensor is properly
connected.
Make sure that the evaporator temperature sensor is
properly connected.
Make sure that the evaporator motor is properly
connected to the board.
Check for a foreign substance inside the unit that may be
preventing the blower wheel from turning.
Reset the option codes.
Make sure that the service valves are completely open.
Check for any blockage in the refrigerant pipe that
connects the indoor and outdoor units.
Check for refrigerant leaks.
Make sure a sufficient amount of refrigerant has been
added for a pipe that is longer than 7.5 m.
Check for refrigerant leaks between the valve and pipe
connection.
1
2
Measures for the installer to take
Check the following:
Strength of the installation site
Tightness of pipe connection to detect gas leak
Electric wiring connection
Heat-resistant insulation of the pipe
Drainage
Grounding conductor connection
Correct operation (Take the following steps.)
Press the
(Power) button on the remote control to
check the following:
The indicator on the indoor unit lights up.
The airflow blade opens and the fan gears up for
operation.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents