Step 4-4 Adding Refrigerant (If Needed); Step 4-5 Important Information: Regulation Regarding The Refrigerant Used - Samsung AR TXHZ Series Installation Manual

Hide thumbs Also See for AR TXHZ Series:
Table of Contents

Advertisement

Installation Inspection and Testing

Step 4-4 Adding refrigerant (if needed)

The outdoor unit is charged with sufficient R-32 refrigerant to
support up to a 5 m line set. For lengths greater than 5 m,
you must add 15 g of refrigerant per meter of additional
length, after the lines are evacuated.
1
Calculate the additional refrigerant required:
Additional grams of R-32 = (Total line set meter − 5) × 15
2
Connect the common hose of the manifold gauge set to
the inverted R-32 refrigerant cylinder.
3
Place the refrigerant cylinder on a scale set to measure
grams.
4
Open the valve on the tank.
5
At the manifold connection, bleed the refrigerant to
remove any air that may be present in the common hose.
6
Open the gauge manifold and charge the system with the
amount of refrigerant calculated in step 1.
7
Close the gauge manifold valve, close the valve on the
refrigerant tank, and remove the common hose.
Precautions on adding the R-32 refrigerant
In addition to the conventional charging procedure, the
following requirements shall be kept.
Make sure that contamination by other refrigerants
does not occur for charging.
To minimize the amount of refrigerant, keep the hoses
and lines as short as possible.
The cylinders shall be kept upright.
Make sure that the refrigeration system is earthed
before charging.
Label the system after charging, if necessary.
Extreme care is required not to overcharge the system.
Before recharging, the pressure shall be checked with
nitrogen blowing.
After charging, check for leakage before commissioning.
Be sure to check for leakage before leaving the work
area.
26
English
Step 4-5 Important information:
regulation regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do not
vent gases into the atmosphere.
CAUTION
Inform user if the system contains 5 tCO₂e or more of
fluorinated greenhouse gases. In this case, it must be
checked for leakage at least once every 12 months,
according to regulation No. 517/2014. This activity must
be covered by qualified personnel only. In the case of
the situation above, the installer (or authorized person
with responsibility for final check) must provide a
maintenance book, with all the information recorded,
according to REGULATION (EU) No. 517/2014 OF THE
EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16
April 2014 on fluorinated greenhouse gases.
1
Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product and on
this manual.
the factory refrigerant charge of the product,
the additional refrigerant amount charged in
the field and
+
the total refrigerant charge. on the
refrigerant charge label supplied with the product.
Refrigerant type
R-32
• GWP: Global Warming Potential
• Calculating tCO₂e: kg x GWP/1000
Indoor unit
Unit
①, a
②, b
①+②, c
GWP value
675
Outdoor unit
Kg
tCO₂e