Page 1
Einbauanleitung Dezentrales Lüftungssystem mit Wärmerückgewinnung Typen e², e²kurz und e²neo - Bitte an den Nutzer weiterleiten - Installation Manual Decentralised Ventilation System with Heat Recovery Type e², e²short and e²neo - Please pass on to user -...
Page 2
Assembly: Electric installation and Electric connection Assembly: Heat recovery unit and Inner screen Assembly: Sound insulation set Replacement of ALD-R 160 by e², Note on LUNOS Outer covers Filter replacement, Cleaning, Additional parts and Replacement parts About this manual ...
Page 3
Dimension diagrams (all dimensions in mm) 300 - 700 DA 160 Heat exchanger 200* –300 Dimensions in mm Heat exchanger ring e²short : *Shorten EPP ring if necessary Installation position Decentralised ventilation devices with heat recovery of the type e² only function in pairs in bidirectional operation.
Operating range Temperature range: -15°C to +40°C Usable with relative humidity levels of up to 65% in the interior area. During heating periods low levels of condensate formation may occur. When usage limits are exceeded, switch off the device and close the inner screen.
Page 5
Assembly: Assembly pipe and outer grille ① Make the wall openings for the as- sembly pipes (e.g. by coring, core bit Ø 162 mm). If necessary shorten the pipe to the required installation length (e²: min. 300 mm; e²short: min. 200 mm). Plaster protection cap Take care that the pipe overlaps on Indoors...
Electric connection only by a specialist. Additional installations and electrical components in this ventilation system are not allowed. ➃ The system can be controlled via Device 1 Device 2 several controls of LUNOS. Supply/Exhaust Exhaust/Supply Follow the relevant installation instructions. Connector box Select the position of the switch.
Page 7
Assembly: Heat recovery unit and Inner screen ⑥ Motor Remove plaster protection cap inside, insert heat exchanger unit into the assembly pipe, ensure there is a 22 mm spacing. Motor is on the inside. Using the loop on the inside of the heat exchanger unit the said unit may be pulled out for correction purposes.
Page 8
5 onward. Note on LUNOS outer covers The full-plastic outer covers supplied by LUNOS provide high resistance to driving rain and meet the reqirements of Stress Group III according to DIN 4108-3 (2014-11). Metallic or metal-coated covers can be used in Stress Group I in accordance with DIN 4108-3 (2014-11).
Page 9
W1 for 3 seconds. For the functionality of the filter change indicator in connection with the TAC or the LUNOS-KNX Control please see the LED iIluminates beneath the switch corresponding instructions. Please note below information on the filter changes you have carried out:...
Page 10
The product’s installation shall not conflict with any requirement in the National Electrical Code, ANSI/NFPA 70-1999. Additional installations and electrical components in this ventilation system are prohibited! LUNOS Germany LUNOS Lüftungstechnik GmbH Phone +49 30 362 001-0 für Raumluftsysteme +49 30 362 001-89 Wilhelmstr.