Appendix B – Technical Data
B-4
Connectors:
• Light transmitter (grey) and receiver (blue) for connection to the
drive
• Two Combicon MVSTBW 2,5/8-ST-5,08 (8-pole, cross-section
2
2.5 mm
max.) screw terminal blocks for the fieldbus and power
supply:
X1 (IN)
1
0V
Power supply for the module
24 V d.c. ± 10 %; maximum power consumption 160 mA
2
+24V
3
DG1
Signal Ground
4
/DI1
Data in 1 (Inverted)
5
DI1
Data in 1
6
/DO1
Data out 1 (Inverted)
7
DO1
Data out 1
8
SHF
Filtered Shield (Connected to module earth via an RC filter)
X2 (OUT)
1
SH
Shield (Module earth)
2
DI2
Data in 2
3
/DI2
Data in 2 (Inverted)
4
DO2
Data out 2
5
/DO2
Data out 2 (Inverted)
6
DG2
Signal Ground
7
RBST
Remote Bus Connector
8
RB5V
Signal +5V
General:
• All materials are UL/CSA approved
• Complies with EMC Standards EN 50081-2 and EN 50082-2