INSTALLATION AND MAINTENANCE INSTRUCTIONS
1412B and 1424 Direct Wire
Ionization Smoke Detectors
Specifications
Diameter:
Height:
Weight:
Operating Temperature:
Operating Humidity:
Locking Alarm:
Relay Contact Ratings
Resistive or Inductive (60% power factor) load
Form A:
Form C:*
*For Canadian installations, relay contact rating is 2.0A @ 30VAC/DC
Electrical Ratings:
System Voltage:
Supply Voltages:
Reset Voltages:
Standby Current:
Alarm Currents:
The alarm and auxiliary relay operate within the specified voltage ratings.
Reset Time:
Start-up Time:
Before Installing
Please thoroughly read the System Sensor manual A05-
1003, Applications Guide for System Smoke Detectors,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available at no charge from System
Sensor. (For installation in Canada, refer to CAN/ULC-
S524, Standard for the Installation of Fire Alarm Systems
and CEC Part 1, Sec. 32.)
General Description
System Sensor 1412 and 1424 dual-chamber ionization
smoke detectors utilize state-of-the-art, unipolar sensing
chambers. These detectors are designed to provide open
area protection, and to be used with UL-listed 4-wire con-
trol panels. The 1412 for 12 volt panels operates at 12VDC,
and the 1424 for 24 volt panels operates at 24VDC. The
detectors' operation and sensitivity can be tested in place.
These detectors are listed to UL 268 and are latching type
system detectors. When latched in alarm, the detectors
must be reset by a momentary power interruption.
D400-08-00
5.5 inches (14 cm)
3.12 inches (8.0 cm)
0.7 lb (310 gm)
0°C to +49°C (32°F to 120°F)
10% to 93% Relative Humidity Non-condensing
Reset by momentary power interruption.
2.0A @ 30VAC/DC
0.6A @ 110VDC, 2.0A @ 30VDC
1.0A @ 125VAC, 2.0A @ 30VAC
1412
12
11.3
17.3
.73
100
35.2
77.0
0.3
30
An LED on the detector provides a local indication of the
detector's status. If power is applied to the detector, and
the detector is functioning properly in standby, the status
LED will blink every 10 seconds. In alarm, the LED will be
latched on continuously until the detector is reset.
Each detector contains one Form A (SPST-NO) contact for
connection to the alarm-initiating circuit, and one Form
C (SPDT-NO/NC) set of auxiliary contacts. Supervision
of detector power is accomplished by installing a Power
Supervisory End-of-Line Relay Module (A77-716) at the end
of the detector power loop. When power is applied to and
through the detectors, the EOL Power Supervisory Module
is energized. Its relay contacts close and provide a closed
series circuit in the control panel's alarm-initiating loop. A
power failure or a break in the detector power loop de-ener-
gizes the EOL Module. The relay contacts open and trigger
a trouble signal at the control panel.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
1424
24
DC (4V Maximum Ripple)
20
VDC Minimum
29
VDC Maximum
.8
VDC Minimum
100
µA Maximum
21.3
mA Minimum
40.6
mA Maximum
0.3
Seconds
30
Seconds
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
I56-280-05R

Advertisement

loading
Need help?

Need help?

Do you have a question about the 1412B and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor 1412B

  • Page 1 Seconds Before Installing An LED on the detector provides a local indication of the Please thoroughly read the System Sensor manual A05- detector’s status. If power is applied to the detector, and 1003, Applications Guide for System Smoke Detectors, which provides detailed information on detector spacing, the detector is functioning properly in standby, the status placement, zoning, wiring, and special applications.
  • Page 2: Wiring Installation Guidelines

    Figure 1. Flush mounting of detector on 4 inch Figure 2. Detector mounting bracket: octagonal box: TAMPER RESISTANT S0139-00 TO MAKE DETECTOR TAMPER RESISTANT, BREAK OFF TAB EXTENSION AT SCRIBED LINE S0140-00 Mounting NOTE: Refer to releasing device manufacturer’s installa- Each 1412 and 1424 detector is supplied with a mounting tion instruction for proper connections.
  • Page 3 4. Reset the detector at the system control panel. 3. Turn the detector clockwise until it clicks into place. B. Test Module (System Sensor Model No. MOD400R) 4. After all detectors have been installed, apply power to The MOD400 or MOD400R is used with an analog or the control unit.
  • Page 4 Please include a note describing the malfunction and suspected cause period of three years from date of manufacture. System Sensor makes no of failure. The Company shall not be obligated to repair or replace units other express warranty for this smoke detector.