INSTALLATION AND MAINTENANCE INSTRUCTIONS
1400 Direct Wire Ionization

Smoke Detector

Specifications
Diameter:
Height:
Weight:
Operating Temperature:
Latching Alarm:
Operating Humidity:
Electrical Ratings:
System Voltage:
Maximum Ripple Voltage:
Start-up Capacitance:
Standby Ratings:
Alarm Ratings:
Reset Voltage:
Reset Time:
Start-up Time:
Before Installing
Please thoroughly read the System Sensor manual I56-407-
XX, Guide for Proper Use of System Smoke Detectors. This
manual provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available at no charge from System
Sensor. (For installation in Canada, refer to CAN/ULC-
S524, Standard for the Installation of Fire Alarm Systems
and CEC Part 1, Sec. 32.)
General Description
System Sensor 1400 dual-chamber ionization smoke detec-
tors utilize state-of-the-art, unipolar sensing chambers.
These detectors are designed to provide open area protec-
tion, and to be used with compatible UL-listed, 2-wire con-
trol panels only. The detector's operation and sensitivity
can be tested in place.
D400-07-00
5.5 inches (140 mm)
3.12 inches (80 mm)
0.7 lb. (310 g)
0 o to +49 o C (32 o F to 120 o F)
Reset by momentary power interruption.
10% to 93% Relative Humidity, Noncondensing
12/24 VDC
4 Volts peak to peak
0.02 µA Maximum
8.5 VDC Minimum
35 VDC Maximum
100 µA Maximum
4.2 VDC Minimum at 10 mA
6.6 VDC Minimum at 100 mA
Alarm current must be limited to 100 mA maximum by the control panel. If used, the
RA400Z Remote Annunciator operates within the specified detector alarm currents.
2.5 VDC Minimum
0.3 S Maximum
35 S Maximum
1
Each detector includes an LED that provides a local visual
indication of the detector's status. The LED blinks every ten
seconds as an indication that power is applied to the detec-
tor and lights continuously in alarm. These detectors also
have the latching alarm feature. The alarm can be reset
only by a momentary power interruption.
The detector also has provision for the connection of an
optional Model RA400Z Remote Annunciator. The RA400Z
provides a visual indication of an alarm and mounts to a
single gang box.
Spacing
NFPA 72 defines the spacing requirements for smoke detec-
tors. Typically, this is 30 feet when the detectors are
installed on a smooth ceiling. However, ALL installations
must comply with NFPA 72 and/or special requirements of
the authority having jurisdiction.
3825 Ohio Avenue
St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
I56-279-04R

Advertisement

loading
Need help?

Need help?

Do you have a question about the 1400 and is the answer not in the manual?

Questions and answers

Summary of Contents for System Sensor 1400

  • Page 1: Smoke Detector

    Before Installing Each detector includes an LED that provides a local visual Please thoroughly read the System Sensor manual I56-407- indication of the detector’s status. The LED blinks every ten XX, Guide for Proper Use of System Smoke Detectors. This...
  • Page 2 To remove the detector from the brack- Mounting et once it has been made tamper resistant, use a small Each 1400 detector is supplied with a mounting bracket kit screwdriver to depress the tamper-resistant tab located in that permits the detector to be mounted: the slot on the mounting bracket and turn the detector 1.
  • Page 3 Figure 3. Wiring diagram for 1400 smoke detector used with two-wire control panel: INITIATING LOOP – – – RESISTOR UL LISTED COMPATIBLE CONTROL REMOTE REMOTE PANEL ANNUNCIATOR ANNUNCIATOR – – A78-1554-00 CLASS A OPTIONAL WIRING NOTE: IF REMOTE ANNUNCIATOR IS NOT USED, POLARITY TO DETECTOR MAY BE REVERSED.
  • Page 4 Please include a note describing the malfunction and suspected cause of period of three years from date of manufacture. System Sensor makes no failure. The Company shall not be obligated to repair or replace units other express warranty for this smoke detector.