INSTALLATION AND MAINTENANCE INSTRUCTIONS
1251B Plug-in Intelligent Ionization
Sensor with Communications
Specifications
Operating Voltage Range:
Max. Avg. Standby Current:
Max. Alarm Current (LED on):
Operating Humidity Range:
Operating Temperature Range:
Height:
Diameter:
Weight:
Before Installing
This sensor must be installed in compliance with the con-
trol panel system installation manual. The installation must
meet the requirements of the Authority Having Jurisdiction
(AHJ). Sensors offer maximum performance when installed
in compliance with the National Fire Protection Association
(NFPA); see NFPA 72.
General Description
Model 1251B intelligent ionization sensor uses a state-of-
the-art sensing chamber. These sensors are designed to
provide open area protection and are intended for use with
compatible control panels only.
Two LEDs on each sensor light to provide a local, visible
sensor indication. Remote LED annunciator capability is
also available as an optional accessory (RA400Z).
The 1251B requires compatible addressable communica-
tions to function properly. Connect this sensor to listed-
compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compliance
with NFPA 72. In low air flow applications with smooth
ceilings, space sensors 30 feet apart. For specific infor-
mation regarding sensor spacing, placement, and special
applications, refer to NFPA 72 or the System Smoke Detector
Application Guide, available from System Sensor.
Wiring Guide
All wiring must be installed in compliance with the
National Electrical Code, applicable local codes, and any
special requirements of the Authority Having Jurisdiction.
D200-28-00
15 to 32 VDC
300µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)
6.5 mA @ 24 VDC
10% to 93% Relative Humidity, non condensing
0°C to 49°C (32°F to 120°F)
2.0 inches (51 mm) installed in B210LP Base
6.1 inches (155 mm) installed in B210LP Base
4.1 inches (104 mm) installed in B501 Base
5.4 oz. (153 g)
1
3825 Ohio Avenue, St. Charles, Illinois 60174
Proper wire gauges should be used. The installation wires
should be color-coded to limit wiring mistakes and ease
system troubleshooting. Improper connections will prevent
a system from responding properly in the event of a fire.
Remove power from the communication line before
installing sensors.
1. Wire the sensor base (supplied separately) per the wir-
ing diagram, see Figure 1.
2. Set the desired address on the sensor address switches,
see Figure 2.
3. Install the sensor into the sensor base. Push the sensor
into the base while turning it clockwise to secure it in
place.
4. After all sensors have been installed, apply power to the
control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section
of this manual.
Dust covers provide limited protection against airborne dust
particles during shipping. Dust covers must be removed
before the sensors can sense smoke. Remove sensors prior
to heavy remodeling or construction.
Tamper-Resistance
Model 1251B includes a tamper-resistant capability that
prevents their removal from the bracket without the use of
a tool. Refer to the base manual for details on making use
of this capability.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
CAUTION
I56-1908-02R

Advertisement

loading
Need help?

Need help?

Do you have a question about the 1251B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for System Sensor 1251B

  • Page 1 General Description 1. Wire the sensor base (supplied separately) per the wir- Model 1251B intelligent ionization sensor uses a state-of- ing diagram, see Figure 1. the-art sensing chamber. These sensors are designed to 2. Set the desired address on the sensor address switches, provide open area protection and are intended for use with see Figure 2.
  • Page 2 Figure 1. Wiring Diagram: REMOTE ANNUNCIATOR CAUTION: Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connections. CLASS A OPTIONAL WIRING C0129-00 Testing 2. The sensor should alarm the panel. Before testing, notify the proper authorities that the system Two LEDs on the sensor are controlled by the panel is undergoing maintenance, and will temporarily be out of to indicate sensor status.
  • Page 3 Figure 2. Rotary decade address switches: Test Magnet Magnet Test Position Marker TENS ONES C0146-00 LED Status Indicators Figure 3. Test Magnet positioning: Test Magnet Magnet Test Position Marker Magnet Test Marker Test Magnet Position LED Status Indicators C0145-00 Figure 4: Cleaning Magnet Test Before cleaning, notify the proper authorities that the sys-...
  • Page 4 The Company shall not be obligated to repair or replace units period of three years from date of manufacture. System Sensor makes no which are found to be defective because of damage, unreasonable use, other express warranty for this smoke detector.