Pump protection. To enable seizure
protection on pumps/valves connected to
the HC, select 'Yes'.
Configure pump protection?
No
Yes
Configure pump protection?
No
Yes
DHW priority. If the HC is requried to
give priority to any DHW demands in the
system then select 'Yes'.
DHW priority?
No
Yes
DHW priority?
No
Yes
Operating mode. The operating mode of
the HC can be set from a scrolling field,
once this is set then the HC configuration
is completed by selecting 'Done'.
Operating mode
Standby
Done
Operating mode
Time clock single day
Done
Operating mode
Time clock multiple day
Done
Operating mode
Day
Done
Operating mode
Night
Done
Installation & Servicing
SECTION 2 - INSTALLATION
The HC has now been configured and the
display will return to:
Select HC to configure
HC1 Boiler1.1 ü
Done
Note, that the HC number now has a
tick next to it showing that it has been
configured. If you have completed the
HC configuration, select 'Done'.
Select HC to configure
HC1 Boiler1.1 ü
Done
DHW Configuration
DHW circuit selection for configuration.
Select the DHW circuit from the available
DHW circuits in the list:
Select DHW to configure
DHW1 Boiler 1
Done
DHW pump location. If the DHW circuit has
an individual DHW Pump connected then
select the output that is used to control it
from the list. Otherwise select 'None'.
Select loc'n of DHW pump
None
PWM/0-10V ()
MFR1 ()
Select loc'n of DHW pump
None
PWM/0-10V ()
MFR1 ()
MFR2 ()
Select loc'n of DHW pump
PWM/0-10V ()
MFR1 ()
MFR2 ()
MFR3 ()
Select loc'n of DHW pump
MFR1 ()
MFR2 ()
MFR3 ()
MFR4 ()
Select loc'n of DHW pump
MFR2 ()
MFR3 ()
MFR4 ()
Select loc'n of DHW pump
MFR3 ()
MFR4 ()
Example, MFR2 as a DHW pump:
Select loc'n of DHW pump
MFR1 ()
MFR2 (DHW1 pump)
MFR3 ()
MFR4 ()
The DHW maximum tank temperature set-
point can be set, it defaults to the maximum
DHW output of the boiler model, but this
can be decreased:
Set max tank temp
60 º C
Done
Set max tank temp
60 º C
Done
Antilegionella. If the DHW tank requires
the Antilegionella function then select
either 'Weekday' or 'Interval' from the list.
Otherwise set to 'None'.
Antilegionella?
None
Weekday
Interval
Antilegionella?
None
Weekday
Interval
For weekday set the following parameters,
followed by 'Done':
Antilegionella timing
Weekday: Saturday
Start time: 01:00
Done
Antilegionella timing
Weekday: Saturday
Start time: 01:00
Done
Antilegionella timing
Weekday: Saturday
Start time: 01:00
Done
Then set the desired Antilegionalla
temperature, followed by 'Done':
Antilegionella temperature
65 º C
Done
Antilegionella temperature
65 º C
Done