2) Outdoor unit parameters observation
SW9 is used to select outdoor unit number, SW10 and SW11 working together to show outdoor parameter.
For example, SW9 is set as 0, that shows No.0 outdoor parameter; set as 1, that shows No.1 outdoor parameter...
(Master unit can display the other outdoor parameter and indoor parameter, but the slave unit only displays its own
parameter).
Start up for commissioning, search slave units and display flashing 0 from left to right. If one slave unit is found, display
1; two slave units are found, display 2; and so on, the max. number is 8. After searching slave units, display outdoor
failure code; if no failure, display 0. 0~2 of SW9 are used to select outdoor unit number.
SW9
SW10
SW11
Unit No.
0
0
0-3
1
0
2
5
7
8
9
10
11
12
13
14
15
Function
Display outdoor failure code
Display priority and capacity of
outdoor units
Display priority and capacity of
0
outdoor units
Current frequency of INV
0
compressor
0
Outdoor LEVa1 valve open angle
0
Outdoor LEVa2 valve open angle
0
Outdoor LEVb1 valve open angle
0
Outdoor LEVc valve open angle
Outdoor solenoid valve output
0
indication
Outdoor solenoid valve output
0
indication
Outdoor solenoid valve output
0
indication
0
Heater output
0
Program version
Digital tube LD1- 4 display
Failure code is transmitted by outdoor bus data. If no failure, display the
time in stopwatch counting down from the 6th hour for electrical heating.
Press SW2(UP) for 2 secs continuously, displaying 1111, then come into
historical failure inquiry state. 10 failures happened recently can be
checked. Blinking display the failure number and code. Press SW2(UP)
once to show the next one and press SW1(DOWN) once to show the
previous one.
Exit the setting mode automatically after 2 mins.
Press SW1(DOWN) for 2 secs continuously, displaying 0000 to exit the
inquiry state and stop blinking;
DIP switch plate shows 13,0,0. Press SW2(UP) for 2 secs continuously,
displaying "1111" can eliminate the historical failure records.
LD1 displays the priority of outdoor units
LD2 displays "-"
LD3-4 displays the capacity of outdoor units (unit: HP)
LD1: 0: stop C: cooling H: heating
LD2-LD4: 60 represents 60% of capacity output
110.0: 110.0Hz
Press SW2(UP) for 2 secs continuously, display 1111 then come into
the setting state with blinking display: press SW2(UP) once and the
frequency will increase 1Hz; press SW1(DOWN) once and the frequency
will decrease 1Hz; exit the setting state automatically after 5 mins.
Press SW1(DOWN) for 2 secs continuously, displaying 0000 to exit the
setting state and stop blinking.
(Compressor is forbidden to start up when there are system failures)
0---470 steps
Press SW2(UP) for 2 secs continuously, displaying 1111 then come into
the setting state with blinking display: press SW2(UP)and the valve is fully
opened; press SW1(DOWN) and the valve is fully closed; exit the setting
state automatically after 2 mins.
Press SW1(DOWN) for 2 secs continuously, displaying 0000 to exit the
setting state and stop blinking.
LD1: 4WV : 1 on 0 of--the far left side of the high position
LD2: SV1 : 1 on 0 off
LD3: SV3i : 1 on 0 off
LD4: SV31 : 1 on 0 off
LD1: SV6: 1 on 0 off--the far left side of the high position
LD2: SV9: 1 on 0 off
LD3: SV10: 1 on 0 off
LD4: SV11: 1 on 0 off
LD1: SV18i: 1 on 0 off--the far left side of the high position
LD2: SV181: 1 on 0 off
LD3: SV21: 1 on 0 off
LD4: WV42: 1 on 0 off
LD1: CHi: 1 on 0 off--the far left side of the high position
LD2: CH1: 1 on 0 off
LD3: CH2: 1 on 0 off
LD4: Cha: 1 on 0 off
1.0: Ver1.0