ABB FSCA-01 Manual page 43

Modbus protocol, rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

Register Address*, **
400101-409999
* 6-digit register addressing (400001) is used instead of 5-digit
register addressing (40001) to describe register map. See section
Register addressing
** Register addresses of the 32-bit parameters cannot be
accessed by using 5-digit register numbers.
Register Data (16-bit)
Drive Parameter Access (16-bit)
Register Address = 400000 + 100 x Group + Index
Example for Drive Parameter 3.18
400000 + 100 x 3 + 18 = 400318
Register addressing of the 32-bit parameters (not
supported with ACS350):
420000 + 200 x Group + 2 x Index
Example for Drive Parameter 1.27
420000 + 200 x 1 + 2 x 27 = 420254