ABB FSCA-01 Manual page 15

Modbus protocol, rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

1 FBA TYPE
This parameter shows the fieldbus adapter type as detected by
the drive.
If this parameter is undefined, the communication between the
drive and the module has not been established.
2 PROTOCOL/PROFILE
Selects the application protocol and communication profile for the
network connection.
(0) Modbus protocol with ABB Drives Classic profile
(1) Modbus protocol with ABB Drives Enhanced profile
(2) Modbus protocol with Transparent 16-bit profile
(3) Modbus protocol with Transparent 32-bit profile
3 STATION ID
Defines the address of the device. Two units with the same
address are not allowed on-line.
4 BAUD RATE
Defines the baud rate of the link.
(0) 9.6 kbit/s
(1) 19.2 kbit/s
(2) 38.4 kbit/s
(3) 57.6 kbit/s
(4) 115.2 kbit/s
15
Drive configuration

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents