ABB FSCA-01 Manual page 14

Modbus protocol, rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

14
Table 1. FSCA-01 configuration parameters - group A *
Par. no.
Parameter name
1
FBA TYPE
2
PROTOCOL/
PROFILE
3
STATION ID
4
BAUD RATE
5
PARITY
6
MODBUS TIMEOUT
7
TIMEOUT MODE
8
OK MESSAGES
9
CRC ERRORS
10
UART ERRORS
11... 26
Reserved
* Actual parameter group number depends on the drive type. Eg,
group A equals to parameter group 51 in ACS350 and ACSM1.
Drive configuration
Alternative settings
(Read-only)
Modbus:
(0) ABB Drives Classic
(1) ABB Drives Enhanced
(2) Transparent 16-bit
(3) Transparent 32-bit
1...247
(0) 9.6 kbit/s
(1) 19.2 kbit/s
(2) 38.4 kbit/s
(3) 57.6 kbit/s
(4) 115.2 kbit/s
(0) 8 NONE 1
(1) 8 NONE 2
(2) 8 EVEN 1
(3) 8 ODD 1
0...65535
(0) NONE
(1) ANY MESSAGE
(2) CONTROL WRITE
0...65535
0...65535
0...65535
Default setting
RS-485
Modbus:
(0) ABB Drives
Classic
1
(0) 9.6 kbit/s
(0) 8 NONE 1
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents