ABB FSCA-01 Manual page 31

Modbus protocol, rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

Bit
Name
5
RAMP_HOLD
6
RAMP_IN_
ZERO
7
RESET
8 to 9 Reserved.
10
REMOTE_
CMD
11
EXT_CTRL_
LOC
12 to
Drive-specific (For information, see the drive documentation.)
15
Value
1
Enable ramp function.
Proceed to RAMP FUNCTION GENERATOR:
ACCELERATOR ENABLED.
0
Halt ramping (Ramp Function Generator output
held).
1
Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Force Ramp Function Generator input to zero.
0=>1 Fault reset if an active fault exists. Proceed to
SWITCH-ON INHIBITED.
Note: This bit is effective only if the fieldbus interface
is set as the source for this signal by drive
parameters.
0
Continue normal operation.
1
Fieldbus control enabled.
0
Control Word <> 0 or Reference <> 0: Retain last
Control Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus
control enabled. Reference and deceleration/
acceleration ramp are locked.
1
Select External Control Location EXT2. Effective if
control location parameterised to be selected from
fieldbus.
0
Select External Control Location EXT1. Effective if
control location parameterised to be selected from
fieldbus.
STATE/Description
Communication profiles
31