System Sensor BEAM1224 Installation And Maintenance Instructions Manual page 10

Single-ended reflected type projected beam smoke detector
Table of Contents

Advertisement

NOTE: If the outer aesthetic ring has been painted insure
that the paint is completely dry before proceeding
with this step.
Step 4. Final Verification
This step is required to insure the detector has been setup
correctly and will detect smoke at the proper sensitivity
level.
1. With the detector functioning (indicated by the green
LED blinking), completely block the reflector with an
opaque material. (Due to the high optical efficiency of
the reflector the selection of the opaque material used
to block the reflector is not critical. Acceptable materials
include, but aren't limited to, this manual or the card-
board packaging inserts.) See Figure 14. The detector
should enter the trouble condition (indicated by the
fault relay and the yellow LED (see Appendix I). If the
detector does not enter the trouble condition there is a
problem with the installation refer to the troubleshoot-
ing section in Appendix I for further assistance.
2. Complete a sensitivity test of the detector. Refer to the
Sensitivity Testing section of this manual for the appro-
priate procedure.
3. If the orange sticky paper was used to aid in the loca-
tion of the reflector in the alignment mirror it should be
removed now. It is no longer necessary.
Congratulations. You have completed the final installation
and alignment procedure.
Figure 10. Switch Locations
D400-73-00
Figure 11. Alignment Adjustment Locations
OPTICS
LOCK-DOWN
SCREWS
Figure 12. Coarse Alignment Procedure
ALIGNMENT
SENSITIVITY
TEST
RESET
C0274-00
10
ALIGNMENT MIRROR
ALIGNMENT
POSITION
INDICATOR
VERTICAL
ADJUSTMENT
ALIGNMENT GUNSIGHT
DIGITAL SIGNAL
STRENGTH
READOUT
HORIZONTAL
ADJUSTMENT
C0264-00
EYE
REFLECTOR
C0625-00
I56-2294-03R

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Beam1224s

Table of Contents