1. Certificate number DEMKO 13 ATEX 1207259X
2. Ambient range (-40°C ≤ Tamb ≤ 75°C)
3. Certification string (Ex nA nC IIC T3 Gc)
4. Standards covered (EN 60079-0:2012+A11:2013, EN 60079-15:2010)
5. The conditions of safe usage:
 The Ethernet Communication Devices are to be mounted in an IP54
enclosure and used in an area of not more than pollution degree 2 as
defined by IEC60664-1.
 A 4 mm² conductor must be used when connection to the external
grounding screw is utilized
 Conductors suitable for use in an ambient temperature greater than
91°C must be used for the power supply terminal.
 Provisions shall be made, either in or external to the apparatus, to
prevent the rated voltage from being exceeded by more than 40% due
to transients disturbances.
7. Pull-high, Pull-low, and Terminator for RS-485
Remove the Serial/Ethernet Converter's top cover and you will find DIP
switches to adjust each serial port's pull-high, pull-low, and terminator.
IE-CS(T)-2TX-1RS232/485

ATEX Information

IE-CS(T)-2TX-2RS232/485
- 7 -