Configuration Wizard: Additional Zone; Detailed Screen With Weather-Dependent Curve; Configuration Wizard: Tank - Daikin Altherma 3 H F EAVH16SU18DA6V Installation Manual

Hide thumbs Also See for Altherma 3 H F EAVH16SU18DA6V:
Table of Contents

Advertisement

5.2.6

Configuration wizard: Additional zone

The most important settings for the additional leaving water zone
can be set here.
Emitter type
For more info about this functionality, see
zone" [ 4  18].
wizard: Main
#
Code
[3.7]
[2‑0D]
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
"5.2.5 Configuration wizard: Main
#
Code
▪ 0: Leaving water if the control type
[3.9]
N/A
of the main zone is Leaving water.
▪ 1: External room thermostat if the
control type of the main zone is
External room thermostat or Room
thermostat.
Setpoint mode
For more info about this functionality, see
zone" [ 4  18].
wizard: Main
#
Code
[3.4]
N/A
▪ 0: Fixed
▪ 1: WD heating, fixed cooling
▪ 2: Weather dependent
If you choose WD
heating,
dependent, the next screen will be the detailed screen with weather-
dependent curves. Also see
"5.2.7  Detailed screen with weather-
curve" [ 4  19].
dependent
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Also see
"5.2.5 Configuration wizard: Main
#
Code
[3.1]
N/A
▪ 0: No
▪ 1: Yes
5.2.7
Detailed screen with weather-dependent
curve
When weather-dependent (WD) operation is active the desired
leaving water or tank temperature is determined automatically
depending on the averaged outdoor temperature. When the outdoor
temperature is lower the leaving water or tank temperature will need
to be higher as the water pipes will be colder and vice versa.
EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606486-1 – 2019.12
"5.2.5  Configuration
Description
zone" [ 4  18].
Description
"5.2.5  Configuration
Description
fixed
cooling or Weather
zone" [ 4  18].
Description
2-points WD curve
The weather-dependent curve is defined by two setpoints:
▪ Setpoint (X1, Y2)
▪ Setpoint (X2, Y1)
Weather-dependent curve:
Y2
Y1
X1
X2
Possible actions on this screen
Go through the temperatures.
Change the temperature.
Go to the next temperature.
Confirm changes and proceed.
Item
a
Selected weather dependent zone:
: Main zone or additional zone heating
: Main zone or additional zone cooling
: Domestic hot water
X1, X2
Examples of outdoor ambient temperature
Y1, Y2
Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:
: Underfloor heating
: Fan coil unit
: Radiator
: Domestic hot water tank
5.2.8

Configuration wizard: Tank

Heat up mode
The domestic hot water can be prepared in 3 different ways. They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.
#
Code
Heat up mode:
[5.6]
[6-0D]
▪ 0:
operation is allowed.
▪ 1: Schedule + reheat: The domestic
hot water tank is heated according to a
schedule and between the scheduled
heat up cycles, reheat operation is
allowed.
▪ 2: Schedule only: The domestic hot
water tank can ONLY be heated
according to a schedule.
See the operation manual for more details.
5 Configuration
a
Description
Description
Reheat
only:
Only
reheat
Installation manual