5 Configuration
Comfort setpoint
Only applicable when domestic hot water preparation is Schedule
only or Schedule + reheat. When programming the schedule, you
can make use of the comfort setpoint as a preset value. When you
later want to change the storage setpoint, you only have to do it in
one place.
The tank will heat up until the storage comfort temperature has
been reached. It is the higher desired temperature when a storage
comfort action is scheduled.
Additionally, a storage stop can be programmed. This feature puts a
stop to tank heating even if the setpoint has NOT been reached.
Only program a storage stop when tank heating is absolutely
undesirable.
#
Code
Comfort setpoint:
[5.2]
[6-0A]
▪ 30°C~[6‑0E]°C
Eco setpoint
The storage economic temperature denotes the lower desired
tank temperature. It is the desired temperature when a storage
economic action is scheduled (preferably during day).
#
Code
[5.3]
[6-0B]
Eco setpoint:
▪ 30°C~min(50,[6‑0E])°C
Reheat setpoint
Desired reheat tank temperature, used:
▪ in Schedule
+
reheat mode, during reheat mode: the
guaranteed minimum tank temperature is set by the Reheat
setpoint minus the reheat hysteresis. If the tank temperature
drops below this value, the tank is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature rises above this value,
domestic hot water preparation and space heating/cooling are
executed sequentially.
#
Code
[5.4]
[6-0C]
Reheat setpoint:
▪ 30°C~min(50,[6‑0E])°C
Installation manual
20
Description
Description
Description
5.3

Settings menu

You can set additional settings using the main menu screen and its
submenus. The most important settings are presented here.
5.3.1

Main zone

Thermostat type
Only applicable in external room thermostat control.
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if [C.2] Space
heating/cooling=On.
#
Code
[2.A]
[C–05]
External room thermostat type for the
main zone:
▪ 1: 1 contact: The used external room
thermostat can only send a thermo
ON/OFF
separation between heating or cooling
demand.
▪ 2: 2
room thermostat can send a separate
heating/cooling
condition.
5.3.2

Additional zone

Thermostat type
Only applicable in external room thermostat control. For more info
about the functionality, see
"5.3.1 Main
#
Code
[3.A]
[C–06]
External room thermostat type for the
additional zone:
▪ 1: 1 contact
▪ 2: 2 contacts
5.3.3

Information

Dealer information
The installer can fill in his contact number here.
#
Code
[8.3]
N/A
Number that users can call in case of
problems.
Description
condition.
There
is
no
contacts: The used external
thermo
ON/OFF
zone" [ 4  20].
Description
Description
EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606486-1 – 2019.12