2.3
Checklist for the required DHW
accessories
For installation compliant with section G3 of the Building
Regulations, you must verify that the following accessories are
present.
Delivered with indoor unit:
Tundish 15 mm inlet, 22 mm outlet
Delivered with domestic hot water tank kit:
Pressure reducing valve/pressure relief valve combination
Adaptor 22 mm×3/4" Female BSP
T-piece 22 mm×22 mm×22 mm
Tundish 15 mm inlet, 22 mm outlet
Wall mounting set for expansion vessel
Instruction sheet
Expansion vessel of 18 L – 3/4" Male BSP
3

Preparation

3.1

Preparing the installation site

WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
3.1.1
Installation site requirements of the
indoor unit
▪ The indoor unit is designed for indoor installation only and for the
following ambient temperatures:
▪ Space heating operation: 5~30°C
▪ Space cooling operation: 5~35°C
▪ Domestic hot water production: 5~35°C
INFORMATION
Cooling is only applicable in case of:
▪ Reversible models
▪ Heating only models + conversion kit (EKHVCONV2)
▪ Mind the measurement guidelines:
Maximum height difference between indoor unit and
outdoor unit
Maximum total water piping length
(a)
Precise water piping length can be determined using the
Hydronic Piping Calculation tool. The Hydronic Piping
Calculation tool is part of the Heating Solutions
Navigator which can be reached via
professional.standbyme.daikin.eu. Please contact your
dealer if you have no access to Heating Solutions
Navigator.
EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606486-1 – 2019.12
▪ Mind the following spacing installation guidelines:
≥100
3.2
3.2.1
Minimum water volume
Check that the total water volume in the installation is minimum 20
litres, the internal water volume of the outdoor unit NOT included.
Minimum flow rate
Check that the minimum flow rate in the installation is guaranteed in
all conditions. This minimum flow rate is required during defrost/
backup heater operation. For this purpose, use the overpressure
bypass valve delivered with the unit.
10 m
(a)
50 m
https://
See the installer reference guide for more information.
Minimum required flow rate
20 l/min
See the recommended procedure as described in
during
≥500
≥650
INFORMATION
If you have limited installation space, do the following
before installing the unit in its final position:
connect the drain hose to the drain" 
remove one or both side panels.

Preparing water piping

NOTICE
In case of plastic pipes, make sure they are fully oxygen
diffusion tight according to DIN  4726. The diffusion of
oxygen into the piping can lead to excessive corrosion.

To check the water volume and flow rate

NOTICE
When circulation in each space heating/cooling loop is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.
NOTICE
To guarantee proper operation it is recommended to have
a minimum flow of 28 l/min during DHW.
NOTICE
If glycol was added to the water circuit, and the
temperature of the water circuit is low, the flow rate will
NOT be displayed on the user interface. In this case, the
minimum flow rate can be checked by way of the pump
test (check that the user interface does NOT display error
7H).
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).
commissioning" [ 4  22].
3 Preparation
(mm)
"4.2.2  To
[ 4   8]. It requires to
"6.2  Checklist
Installation manual
5

Advertisement

Table of Contents
loading