7 Configuration
It is important to set Emitter type correctly and in accordance with
your system layout. The target delta T for the main zone depends on
it.
#
Code
[2.7]
[2‑0C]
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Description
Space heating
setpoint range
0: Underfloor
Maximum 55°C
heating
1: Fancoil unit
Maximum 55°C
2: Radiator
Maximum 70°C
NOTICE
Average
emitter
temperature
temperature – (Delta T)/2
This means that for a same leaving water temperature
setpoint, the average emitter temperature of radiators is
lower than that of underfloor heating because of a bigger
delta T.
Example radiators: 40–10/2=35°C
Example underfloor heating: 40–5/2=37.5°C
To compensate, you can:
▪ Increase
the
weather-dependent
temperatures [2.5].
▪ Enable leaving water temperature modulation and
increase the maximum modulation [2.C].
Control
Define how the operation of the unit is controlled.
Control
Leaving water
Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.
External room
Unit operation is decided by the external
thermostat
thermostat or equivalent (e.g. heat pump
convector).
Room thermostat Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).
#
Code
[2.9]
[C‑07]
▪ 0: Leaving water
▪ 1: External room thermostat
▪ 2: Room thermostat
Setpoint mode
Define the setpoint mode:
▪ Fixed: the desired leaving water temperature does not depend on
the outdoor ambient temperature.
▪ In WD heating, fixed cooling mode, the desired leaving water
temperature:
▪ depends on the outdoor ambient temperature for heating
▪ does NOT depend on the outdoor ambient temperature for
cooling
Installation manual
26
Description
Target delta T in
heating
Variable
Variable
Fixed 10°C
=
Leaving
water
curve
desired
In this control...
Description
▪ In Weather
dependent mode, the desired leaving water
temperature depends on the outdoor ambient temperature.
#
Code
[2.4]
N/A
Setpoint mode:
▪ Fixed
▪ WD heating, fixed cooling
▪ Weather dependent
When weather dependent operation is active, low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user can shift the water
temperature up or down by a maximum of 10°C.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:
▪ In Fixed LWT setpoint mode, the scheduled actions consist of
desired leaving water temperatures, either preset or custom.
▪ In Weather
dependent LWT setpoint mode, the scheduled
actions consist of desired shift actions, either preset or custom.
#
Code
[2.1]
N/A
▪ 0: No
▪ 1: Yes
7.2.6

Configuration wizard: Additional zone

The most important settings for the additional leaving water zone
can be set here.
Emitter type
For more info about this functionality, see
zone" [ 4  25].
wizard: Main
#
Code
▪ 0: Underfloor heating
[3.7]
[2‑0D]
▪ 1: Fancoil unit
▪ 2: Radiator
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
"7.2.5 Configuration wizard: Main
#
Code
[3.9]
N/A
▪ 0: Leaving water if the control type
of the main zone is Leaving water.
▪ 1: External room thermostat if the
control type of the main zone is
External room thermostat or Room
thermostat.
Setpoint mode
For more info about this functionality, see
zone" [ 4  25].
wizard: Main
#
Code
[3.4]
N/A
▪ 0: Fixed
▪ 1: WD heating, fixed cooling
▪ 2: Weather dependent
If you choose WD
heating,
dependent, the next screen will be the detailed screen with weather-
dependent curves. Also see
"7.3 Weather-dependent
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Also see
"7.2.5 Configuration wizard: Main
Description
Description
"7.2.5  Configuration
Description
zone" [ 4  25].
Description
"7.2.5  Configuration
Description
fixed
cooling or Weather
curve" [ 4  27].
zone" [ 4  25].
ETBH/X16E
Daikin Altherma 3 H HT W
4P644727-1B – 2022.03