To Connect The Backup Heater Power Supply - Daikin Altherma 3 H F EAVH16SU18DA6V Installation Manual

Hide thumbs Also See for Altherma 3 H F EAVH16SU18DA6V:
Table of Contents

Advertisement

4 Installation
In case of preferential kWh rate power supply
Connect X11Y to X11YB.
1 2 3
N L
1
2 3
N L
a
b
c
1 2 3
5
6
X11YB
X1M
X11YA
X11Y
X1A
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
2 Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X11Y to X11YB. The necessity of separate normal kWh
rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat.
Thus,
the
preferential kWh rate power supply OR a safety
thermostat.
4.4.4
To connect the backup heater power
supply
WARNING
The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always
connect the backup heater power supply and the earth
cable.
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
Installation manual
12
S1S
X2M
9 10
X5M
system
can
have
EITHER
Backup
Backup
heater type
heater
supply
capacity
*6V
2 kW
1N~ 230 V
4 kW
1N~ 230 V
6 kW
1N~ 230 V
2 kW
3~ 230 V
4 kW
3~ 230 V
6 kW
3~ 230 V
(a)
6V
(b)
Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the
limits for harmonic currents produced by equipment
connected to public low-voltage systems with input
current >16 A and ≤75 A per phase).
(c)
This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and
flicker in public low-voltage supply systems for
equipment with rated current ≤75 A) provided that the
system impedance Z
the interface point between the user's supply and the
public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the
equipment is connected only to a supply with a system
impedance Z
less than or equal to Z
sys
(d)
6T1
Connect the backup heater power supply as follows:
a
X6M
F1B
b
Q1DI
a
Factory-mounted cable connected to the contactor of the
backup heater, inside the switch box (K5M)
b
Field wiring (see table below)
Model (power
Connections to backup heater power
supply)
*6V (6V: 1N~ 230 V)
SWB
F1B
1N~, 50 Hz
230 V AC
Power
Maximum
Z
max
running
current
(a)
9 A
(a)
(b)(c)
17 A
0.22 Ω
(a)
(b)(c)
26 A
0.22 Ω
(d)
5 A
(d)
10 A
(d)
15 A
is less than or equal to Z
at
sys
max
.
max
supply
2
4
6
14
K5M
1
3
5
13
X6M
1
3
5
7
I
I
I
I
2
4
6
8
Q1DI
L
N
EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606486-1 – 2019.12