Important Notes - C-TEC XFP510-32 Installation Manual

32 zone repeater panel
Table of Contents

Advertisement

IMPORTANT NOTES

This equipment must only be installed and maintained by a suitably skilled
and technically competent person.
This equipment is a piece of Class 1 equipment and MUST BE EARTHED.
ALWAYS isolate the panel's mains and battery backup supplies before making
connections to its PCBs.
Items supplied with this panel
• Installation manual - document no. DFU2200502 (this manual)
• Hex key, for unfastening / securing the panel lid
• Electrical accessory pack, containing:-
1 x 20mm 1ATH 250V HRC ceramic fuse (spare primary fuse)
1 x battery jumper link wire
System design
Fire alarm system design is beyond the scope of this document. A basic understanding of general
fire alarm system components and their use is assumed.
Contact the Fire Officer concerned with the property at an early stage in case he has any
special requirements. We strongly recommend that a suitably qualified and competent person
is consulted in connection with the design of the fire alarm system and that the system is
commissioned and serviced in accordance with the laid down specification and national
standards. If in doubt please consult your supplier.
We recommend you read BS 5839: Pt 1: 2002 "Fire Detection and Alarm Systems for Buildings
(Code of Practice for System Design, Installation, Commissioning and Maintenance)" available at
your local reference library or from the BSI. Other national standards of installation should be
referenced where applicable.
Cable types and limitations
All system wiring should be installed to meet current national standards - in the United Kingdom
these are BS 5839 pt 1 : 2002 and BS7671 (Wiring Regulations).
1.5mm
two-core fire resistant screened cable should be used throughout the repeater network
2
installation. This not only shields the data moving up and down the cables from outside interference
but is essential to ensure compliance with EMC regulations. Cables such as FP 200, Firetuff™,
Firecel™ and MICC may be acceptable provided they are properly terminated at the fire panel and
meet national standards / the system specification as applicable. Consult Clause 26 of BS 5839 pt 1 :
2002 for more detailed information on cables, wiring and other interconnections.
Equipment guarantee
This equipment is not guaranteed unless the complete installation is installed and commissioned
in accordance with the laid down national standards (in the UK BS 5839: Pt 1: 2002) by an
approved and competent person or organisation.
Anti-static handling guidelines
Always observe appropriate electro-static handling precautions prior to handling the
panel's PCBs or any other static-sensitive components.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200502 Rev 1 • Page 3 of 8
XFP 32 ZONE REPEATER PANEL