The Dräger Regard 2400 / 2410 Menu; The Menu Flow-Chart - Dräger REGARD 2400 Instructions For Use Manual

Four channel
Hide thumbs Also See for REGARD 2400:
Table of Contents

Advertisement

11. The Dräger REGARD 2400 / 2410 Menu
The Control Unit Dräger REGARD 2400 / 2410 has a menu to check instrument data
or relays output. It's also possible to set the controller to an inhibit mode or to set the average
values off (both temporary for 20 minutes).
Average values: The average values are the result of 16 measurements in a configured time
between 1 and 254 seconds (16 seconds to 1:07 hours together). An alarm is defined when
all 16 measurements are over the alarm threshold or if the value is 16 fold higher than the
alarm threshold.

11.1. The Menu Flow-Chart

The menu has different functions which can be selected by using the F1 and F2 buttons.
There are 6 different menu points to show information or freeze functions. Every function
jumps back to the measuring mode automatically after 20 minutes. Some menu points are
password protected.
The protect password is 1875.
INHI:
Inhibit mode. Freezing all relays at the current status for a time of 20 minutes. Pass-
word protected.
MOFF:
Average value Off. Freezing the average values for the next 20 minutes. Password
protected.
TOUT:
Testing the output relays. Password protected.
SOFT:
Showing the Software Version.
MOD:
Showing communication details like address (MADR), serial comunication (MCON)
and baud rate (MBAU).
LOG:
Showing the status of the datalogger.
On the following 3 pages the menu-structure of the Dräger REGARD 2400 / 2410 is descri-
bed.
To get to the different menu point the buttons F1, F2 or F1+F2 (together) have to be used.
The Dräger REGARD 2400 / 2410 Menu