Download Print this page

olympia electronics GR-8/leds Installation Instructions page 2

Non maintained / maintained emergency luminaires

Advertisement

Installation instructions (wall mounting)
Figure 1
Diffusor
Reflector
2
Plastic base
For fuse ratings
see text
Figure 4
1. To install the device you have to dismantle it carefully with a flat screwdriver as shown on figure 1.
2. Pass the mains cables through the hole (point 1 in figure 2) and secure it with a suitable bracket to
ensure immobilization of the cable at a distance of no more than 5cm from the luminaire's cable
entry. ATTENTION!! To maintain the IP rating, the outer diameter of the power cable must be at
least 8.2 mm².
3. Mount the base plastic on the wall using the included mounting accessories in points 2 and 3 as
shown on figure 2.
4. Connect the battery`s cable with the appropriate terminal (figure 3).
5. Connect the mains cables to the terminal block as shown on figure 4.
6. Refit carefully the removed plastic parts and power on the luminaire.
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery
charging to perform the nominal autonomy.
Battery replacement.
It can be done only by a competent person and after the mains interruption.
1. Dismantle the device (step 1 of the installation instructions).
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 4 of the installation instructions) and place it in
the position of the old one.
4. Follow the step 6 of the installation procedure and power the device.
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Non reversible connection between main pcb and led module
Temperature (tc)
Page 2 from 3
3
Cable
support
4
Figure 2
1
Figure 3
Non maintained
Maintained
operation
operation
GR-8/leds
GR-9/leds
Olympia Electronics S.A
2501159
2.9-3.6VDC
780mW
45 °C max. across the board
923378005_09_008
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
G: Internally illuminated
*90: 1.5 hour duration
180: 3 hours duration
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet,
which accompanies each product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia Electronics or if the buyer
modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia
Electronics has fully agreed to them in writing. Products that have been damaged can be returned to
the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge
the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or
not the buyer the transportation cost.
HEAD OFFICE
72
km. O.N.R. Thessaloniki-Katerini
nd
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr
Page 3 from 3
(*) Maintained operation: The luminaire lights its
illumination source, when it is powered by the mains
power supply or not.
Non Maintained operation: The luminaire lights its
illumination source, only in power supply's failure.
Note!! The installer should fill in, on the specification label,
the letter G if the luminaire is used as a safety sign.
X 1
A G
9
0
*
923378005_09_008

Advertisement

loading

This manual is also suitable for:

Gr-9/leds