Device description
4.3 LED display
Meaning in display mode A, B or C
LED
L1 / L2
L
*
for the X‑300EEC the following applies:
)
● For devices with power supply unit 24 to 48 VDC: Limit voltage = 17 VDC
● For devices with a multiple range power supply unit 100 to 240 VAC / 60 to 250 VDC:
Meaning in display mode D
LED
L1 / L2
L
*
for the X‑300EEC the following applies:
)
● For devices with power supply unit 24 to 48 VDC: Limit voltage = 17 VDC
● For devices with a multiple range power supply unit 100 to 240 VAC / 60 to 250 VDC:
Note
Devices of the X‑300EEC product group
When using only one power supply unit 24 VDC and two 24 VDC power supplies, the LEDs "L1"
and "L2" signal the existence of the power supply L1 and L2.
When using two 24 VDC power supply units, the LEDs "L1" and "L2" signal the existence of the
primary voltage and the secondary voltage for both power supply units. If the power supply is
intact, a fault occurring on a power supply unit on the secondary side can be recognized.
The P1, P2, ... LEDs for the port status
The P1, P2, ... LEDs show information on the status of their port (transmission speed, mode,
port monitoring). The meaning of these LEDs depends on the display mode ("DM" LED).
24
Color
Status
_
off
green
on
-
off
orange
on
green
on
Limit voltage = 46.5 VDC or 80 VAC
Color
Status
_
off
green
on
-
off
orange
on
green
on
Limit voltage = 46.5 VDC or 80 VAC
Meaning
Power supply L1 / L2 lower than 17 V *
Power supply L1 / L2 higher than 17 V *
Power supplies L1 and L2 less than 17 V or not connected.
Power supply L1 or L2 higher than 17 V
(no redundant supply).
Power supplies L1 and L2 higher than 17 V
(redundant supply).
Meaning
Power supply L1 / L2 is not monitored. If L1 / L2 falls below 17
V *
, the signaling contact does not respond.
)
Power supply L1 / L2 is monitored. If L1 / L2 falls below 17
V *
, the signaling contact responds.
)
Power supplies L1 and L2 are not monitored. If L1 or L2 falls
below 17 V, the signaling contact does not respond.
Power supply L1 or L2 is monitored. If L1 or L2 falls below 17
V, the signaling contact responds.
Power supplies L1 and L2 are monitored. If L1 and L2 fall
below 17 V, the signaling contact responds.
Compact Operating Instructions, 11/2019, A5E02661171-15
)
)