St And 2 Nd Generation Ceiling Mount Sensors - Lutron Electronics RadioRA2 Instructions Manual

One-way transmitter frequency changing procedures
Hide thumbs Also See for RadioRA2:

Advertisement

st
nd
1
and 2
LRF2-xCRB
x = O for Occupancy; V for Vacancy
Now that the frequency has been matched up to the Main
Repeater, proceed with device activation as specified in the
RadioRA2 Programming Utility.
Generation Ceiling Mount Sensors
1. Remove the battery from the sensor by
pulling on the small tab next to the
battery compartment and hold in the
Test, Lights ON, and Lights OFF
buttons.
2. Continue to hold all three buttons while
pushing the battery back into place. After
inserting the battery, continue holding the
three buttons for about 3 seconds until the
dome LED flashes rapidly.
3. Press the Lights ON button to try the next
RF channel (15 total). Press the Lights OFF
button to try the previous channel. Press
the Test button to repeat the current
channel.
4. Continue to cycle through the RF channels
until you hear the Main or Aux Repeater
beep. The beep indicates that the proper
RF channel has been identified. At this
point stop pressing any of the buttons that
change the sensor's RF channel!
5. Hold in the Test, Lights ON, and Lights
OFF buttons for about 3 seconds until
the dome LED stops flashing.
3