Table of Contents Section 1: Introduction to the Aqua-Hot AHE-100-02S Introduction ....................... ..Page 6-7 Danger, Warning, Caution, and Note Box Definitions ............Page 6 Section 2: Aqua-Hot Hydronic Heating System Overview Technical Information ......................Page 8 I.D. Label Sample ......................Page 9 Component Overview ....................Page 9-10...
Page 4
If the Aqua-Hot is Black Smoking ................. Page 70 If the Aqua-Hot is Blue/White Smoking ................ Page 71 If one of the Aqua-Hot’s Heating Zones will not get hot ..........Page 72 If there is a lack of domestic continuous hot water ............Page 73 If there is antifreeze leaking ...................
In order for the diesel- zone heating, and engine preheating. Be sure to reference burner to be considered as a heating source by the Aqua-Hot, Figures 3 for a complete component overview. it must have an adequate fuel supply, receive power from the...
Page 7
Until the thermostat signals that where it transfers the heat to the engine to gradually warm it. heat is no longer required, the Aqua-Hot will continue to send the heated antifreeze and water solution through the Additionally, the Aqua-Hot includes a motor-aide feature, loop, which returns the cooled solution to the Aqua-Hot’s...
XHAUST YSTEM EQUIREMENTS Because the Aqua-Hot’s exhaust is hot and must be kept The exhaust must be able to freely exit away from the away from any heat-sensitive material, the exhaust system vehicle without any obstructions. should be checked to ensure that it continues to meet the following requirements: ...
The Diesel Burner control thermostat is installed onto the ature by checking with a digital thermometer. Aqua-Hot’s boiler tank and monitors the temperature of the antifreeze and water heating solution to determine when it is B. Disconnect the control thermostat’s wires from their at operating temperature and when it requires heat.
Page 15
Using a 1/4” nut driver, unscrew the two screws secur- ing the control thermostat to the Aqua-Hot’s boiler tank thermostat mounting bracket. Install the replacement control thermostat into the ther- mostat mounting bracket and secure with the two screws previously removed.
Verify that the boiler tank’s temperature is below 230°F. The Electric Element control thermostat is installed onto the Aqua-Hot’s boiler tank and monitors the temperature of the Locate the AC control thermostat and remove its wires, antifreeze and water heating solution to determine when it is by loosening and removing the screws securing the at operating temperature and when it requires heat.
Page 17
Using a 1/4” nut driver, unscrew the two screws secur- ing the control thermostat to the Aqua-Hot’s boiler tank thermostat mounting bracket. Install the replacement control thermostat into the ther- mostat mounting bracket and secure with the two screws previously removed.
The electric heating element fails to operate. Using a 1/4” nut driver, unscrew the two screws secur- Troubleshooting: ing the thermostat to the Aqua-Hot’s boiler tank thermo- stat mounting bracket. Disconnect all power supplies. Install the replacement thermostat into the thermostat Remove the thermostat access cover.
NOTE: Bypassing the high-limit thermostats is for testing only and must not be used for the Aqua-Hot’s nor- Note: If a screw longer than 1/4” is used to secure the mal functioning.
Check the Aqua-Hot’s antifreeze and water heating solu- tion’s ratio of water to antifreeze. The mixture ratio Troubleshoot the check valves if the following condition has should be approximately 50/50.
Page 21
Reconnect the interior heating zone fitting and line to the replacement check valve. Refill the Aqua-Hot boiler tank with the antifreeze and water heating solution. Test for proper operation NOTE: The Aqua Hot zone circulation pump is not a self priming pump.
OMPONENTS Tempering Valve: Follow the instructions for removing the diesel burner.. The tempering valve for the Aqua-Hot mixes the heated do- Using Channel Lock Pliers, remove the Thermostat and mestic water from the boiler tank with cold domestic water at Bonnet Assembly.
The Zone circulation pump first draw the heated antifreeze COULD CAUSE SERIOUS DAMAGE OR PERSONAL INJURY and water heating solution from the Aqua-Hot’s boiler tank, then propel it through the hydronic heating system’s interior Ensure that the Aqua-Hot has been completely shut heat plumbing.
Page 25
Be sure to review the wiring schematic in appendix A tighten down the union previously loosened. for proper pump wiring. 12. Re-Install the check valve onto the Aqua-Hot zone cir- 15. Refill the Aqua-Hot boiler tank with the antifreeze and culation pump. The arrow on the check valve must water heating solution.
The stir pump circulates the antifreeze and water heating solution within the Aqua-Hot boiler tank in order to ensure If voltage is present and the pump still fails to oper- even-heating of the solution. To accomplish this, the stir...
Engine Preheat Heat Ensure that the Aqua-Hot has been completely shut exchanger, located inside the boiler tank. down and that all power sources have been disconnect- ed.
COULD CAUSE SERIOUS DAMAGE OR PERSONAL INJURY ment. Ensure that the Aqua-Hot has been completely shut If the boiler tank is above 210°F, the Aqua-Hot is at down and that all power sources have been disconnect- operating temperature and requires no heat.
Page 32
Reinstall the Electric Element access cover. Remove the two wires secured to the defective electric heating element by releasing the screw terminals. Refill the Aqua-Hot’s boiler tank with the antifreeze and water heating solution. Using a 1-1/2 inch socket, remove the defective electric heating element from the Aqua-Hot boiler tank.
URNER VERVIEW Diesel-Burner Overview The Aqua-Hot’s diesel-burner is a device that ignites a mix- from the flame is transferred to the antifreeze and water heat- ture of diesel fuel and air within a controlled setting to serve ing solution where it can be used for each system of the Aq- as a heat source.
Page 38
200 (+/- 5) degrees Fahrenheit. NOTE: Whenever the Diesel-Burner is switched off by the VDC Con- trol Thermostat, it will automatically be reactivated once the Aqua-Hot Boiler Tank’s coolant reaches the preset termperature of approximately 175 (+/-) 5 degrees Fahrenheit.
Diesel-Burner and disconnect power could result in serious bodily injury. CAUTION! Be sure to clamp off the Fuel Supply and Return lines at the ports on top of the Aqua-Hot prior to beginning this replacement procedure. Step 1: Turn Off the Diesel Switch Figure 27 1.
Page 41
Step 4: Remove the Diesel Burner from the Aqua-Hot Figure 30a Figure 30b 1. The Diesel-Burner is secured to the Aqua-Hot with two nuts that can be loosened, and swung out of the way by using a 10mm socket wrench with a 10 inch long exten- sion.
Page 42
7: D ECTION ETACHING AND EATTACHING THE IESEL URNER Step 5: Disconnect the Diesel Burner’s Thermostat Wires From the Aqua-Hot Figure 31b Figure 31a Thermostat Access Cover Wire Access Slot 1. Using a Phillips head Screw Driver loosen the screws 1.
NOTE: Before testing the diesel burner motor it is recom- for loose or damaged wire connections. If the C-Plug mended to ensure that the ground post on the Aqua-Hot is harness and connections are in good condition, but the securely tightened.
145 PSI, A. Check the motor home fuel tank for fuel. If the which is required for proper fuel atomization. Ref- fuel level is below 1/4 the Aqua-Hot diesel erence the illustration below for a basic overview burner will not operate.
Page 74
NOTE: To find an antifreeze leak, the system must be Hot (up to operating temperature) Or pressurized to 17 PSI. Inspect the following components on the Aqua-Hot Heating System for Leaks: 1. On the Front-Side of Aqua-Hot - 1. Electric element 2.
2. Supply/Return Ports A. Defective fitting B. Leaking fitting Note: If no leaks are found on the Aqua-Hot, it is possible that there is a leak within the motor home. Check all Heat exchangers, connections, and tubing for leaks. — Page 75 —...
Depending on the plumbing lines diameter and total length it may be necessary to repeat B-J several times C. Place the radiator cap back onto the Aqua-Hot and tight- before any of the solution appears. Be sure to close both the drain valve and the pump manifold valve each time that the boiler tank is refilled D.
Page 87
B. Is the Diesel Fuel liquid or Jelled? C. Are the electrodes properly adjusted? NOTE: The Aqua-Hot can continue to be used for interior zone heating once the domestic water heating system D. When was the last time an Annual Service has been drained and winterized.
If there is a lack of interior Heat: Note: The 120 Volt-AC Electric Heating Element is the Aqua-Hot’s secondary heat source for heating both the interior and/or the domestic hot water during low heat- ing demand situations (such as when moderate ambient temperatures exist and/or when there is a low demand for domestic hot water).
TO ALLOW THE HEATER TO COOL BEFORE SERVICING water heating solution within the expansion tank should only COULD CAUSE SERIOUS DAMAGE OR PERSONAL INJURY be checked when the Aqua-Hot is at maximum operating temperature. To keep the Aqua-Hot running smoothly, it is recommended to have the diesel-burner tuned up annually.
Page 91
Figure E4c Figure E4b 3. The Diesel-Burner is secured to the Aqua-Hot with two nuts that can be loosened, and swung out of the way by using a 10mm socket wrench with a 10 inch long extension. — Page 91 —...
Page 92
Thermostats Diode Wire 4. Carefully pull the Diesel-Burner away from the Aqua-Hot 4 to 5 inches before rotating the burner, and then remove. NOTE: To remove the diesel burner, it may be necessary to disconnect the wires from the control and hi limit thermostats It may also be necessary to disconnect the Diode Wire.
Page 95
Seam on stainless steel tube 1. Reinstall the combustion chamber into the Aqua-Hot. Please note: the seam on the stainless steel tube must be in the “up” position. Failure to do so could result in premature failure of the combustion chamber.
Page 100
NOTE: When reinstalling the diesel burner be careful not to damage the photo disc or bend the electrodes. Also, be careful to not pinch any wires between the burner and the Aqua-Hot Tank. 1. Align the Diesel-Burner with the Aqua-Hot, using the alignment tabs welded on the Aqua-Hot.
Not winterizing the Aqua-Hot when freezing temperatures this procedure for both the hot and cold faucets. are present will result in serious damage to the Aqua-Hot’s Domestic Water Heating System. Also, be sure to use an Turn off Demand Water pump and remove the hose and re- FDA approved, “GRAS”...