Maintenance Schedule ..............6 Aqua-Hot system. System Features ................7 NOTICE signals a situation where potential damage to the Component Cut-Away ..............8 Aqua-Hot could occur. Operational Flowchart..............9 Relay Control Board ..............10 Interior Switch Panel ..............12 Exhaust System Requirements ..........13 Interlock Switch ................14 Fluid Level Sensor ..............15...
Welcome to the Aqua-Hot 250P Service Manual. This manual based) Heating Systems that can provide heat and tank-less, will serve as a guide for diagnosing and repairing the Aqua-Hot, continuous hot water in one small, easy to install package. how to perform standard maintenance, and guide you through troubleshooting procedures to repair the Aqua-Hot.
Page 4
NOTE: Should any additional assistance be needed, please contact the Technical Support Department at 574-AIR-XCEL • DO NOT connect the 12-volt DC power to the Aqua-Hot if the (574-247-9235). vehicle requires welding. • At maximum operating temperature, the coolant will be very hot and scalding.
When the Aqua-Hot is at maximum operating temperature, the an overheat condition until the unit has been serviced by a coolant is very hot. If the Aqua-Hot heating system is accessed, qualifi ed technician. Failure to do so could result in damage scalding by hot vapor or coolant may occur.
NOTE: This product label is attached to the side of the listed in the Recreational Vehicle Industry Association’s Aqua-Hot, and provides a ready reference to specifi cations, (RVIA) ANSI/NFPA 1192 Handbook for Recreational Vehicle test standards, and important safety notices.
DO 15. Boiler Tank NOT remove these panels. Doing so risks irreparable damage to the Aqua-Hot. Only remove the service panel for service. 16. Domestic Hot-Water Coil 17. Interlock Switch 18.
Fuse Functions, Locations, and Ratings: There are three fast-blow fuses included with this relay The relay control board at use in your Aqua-Hot 250 Propane board and may need to be replaced if they cease to function. Series is designed to function in conjunction with the Fenwal The cradles for these fuses are labeled FH1, FH2, and FH3 and Burner Control Card to allow the heater to operate.
The interior switch panel is used to control the two heating the boiler tank if the need arises. A cold boiler tank can expect sources for the Aqua-Hot’s boiler tank. When a switch is to be brought to operating temperature by the electric heating activated, the indicator light on the switch will illuminate.
• Use standard two-inch automotive-type exhaust piping and avoid bends if possible. The Aqua-Hot’s exhaust is hot and must be kept away from any heat-sensitive material. Therefore, the exhaust system should • The 3-inch and 4-inch black pipe nipple and the exhaust...
Monday through Friday, 7am to 4pm Mountain Standard Time. 2. Release the interlock switch from the Aqua-Hot cabinet by pushing in on the locking tabs and pulling the NOTE: Before attempting to troubleshoot any Aqua-Hot interlock switch.
The fl uid expansion bottle is fi lled to at least the “COLD” the Aqua-Hot. This device is intended as a fail-safe measure mark. which will disengage the Aqua-Hot if the fl uid ever drops below a set threshold. The fl uid level sensor is located on the expansion •...
Page 16
Fluid Level 9. Crimp the new faston connectors to the new fl uid level Sensor sensor. 10. Connect these wires to their receptacles on the Aqua-Hot Lower Fitting to harness. Fluid Return Hose 11. Reconnect the overfl ow hose to the upper fi tting.
Take the temperature and when it requires heat. The Aqua-Hot is reading within 12 inches from the painted tank surface considered to be at operating temperature between 155°F and with the thermometer set to “High Emissivity”...
Page 18
9. Refi ll the Aqua-Hot using an external fi ll pump, fi lling 2. Clamp the hoses indicated below with pinch off pliers to through the zone fi ll port.
2. Ensure that the unit has been shut down and completely Introduction: cooled before continuing. 3. Shut off the coach-side power breaker to the Aqua-Hot. The AC high-limit thermostat serves as a safety measure in the event that the electric heating element continues 4.
Page 20
12. Reposition the tempering valve assembly onto its mounting 1. Shut off gas, electric, and water supply to the Aqua-Hot. stud on the left cabinet wall. 2. Disconnect the domestic water inlet and outlet line fi ttings 13.
• The fl uid expansion bottle is fi lled to at least the “COLD” mark. 1. Ensure that the Aqua-Hot has been completely shut down, • Verify that all in-line fuses are functional. all power sources disconnected, and the unit is allowed to cool completely before continuing.
Cutoff Thermostat. Lack of Hot Water 1. If the LTCO indicator light does not illuminate when domestic water is being used or when the Aqua-Hot falls below operating temperature, complete the following: • Using a temperature sensor, verify that the LTCO thermostat is below 90°F.
Page 23
Low-Temp Cutoff Thermostat Replacing the Low-Temperature Cutoff Thermostat: 1. Ensure that the Aqua-Hot has been completely shut down and that all the power sources have been disconnected. 2. Locate the Low-Temperature Cutoff Thermostat on the Failure to disconnect all power supplies and/or allow Aqua-Hot.
Three-Way Valve Three-Way Valve Introduction: The Aqua-Hot has a three-way directional valve to control coolant priority within the unit. This ensures that there will be a supply when heated water is being called for, but can provide interior heating when the need arises.
Page 25
Connect to wire #22 “Faston” connector. Slide the hoses onto the valve and set the constant tension 9. Refi ll the Aqua-Hot’s boiler tank, purging the heating loop clamps back into place. if necessary. Clamp...
6. Using a back-up wrench, unscrew the tempering valve 1. Inspect the tempering valve to ensure that it is not from the Aqua-Hot. Failure to use a back-up wrench could leaking. result in damage to the cold water inlet pipe.
Page 28
Fluid Circulation Pump Replacement Procedure: 1. Ensure that the Aqua-Hot has been completely shut down, all power sources have been disconnected, and that the unit has been allowed to cool completely. Failure to disconnect all power supplies and/or allow 2. Clamp the zone outlet, and the zone return with hose pinch- the unit to cool before servicing could cause serious pliers as shown below.
2. Allow the unit to cool completely. functions to provide supplementary heat to the Aqua-Hot boiler 3. Verify that the Aqua-Hot is connected to an AC power source tank. This is done with an electric element, an electric relay, such as shore power or an AC generator.
Page 30
Aqua-Hot Molex terminal. 9. Refi ll the Aqua-Hot boiler tank with the previously drained • Resistance should be between approximately 11-13 fl uid, add more 50/50 mix of propylene glycol and distilled ohms.
Propane Burner Propane Burner Overview The propane burner operates on standard, readily available The Aqua-Hot’s propane burner is the heart of the Aqua-Hot unit. propane found at a local propane store. The propane burner is the device which ignites and sustains the combustion of a propane-air mixture.
NOTE: If the Aqua-Hot’s coolant • Checking for a fl ame temperature approximately • Checking the Control Thermostat The Control Thermostat 190°F or higher, the Motor will not...
DO NOT INSTALL JUMPER WIRES ACROSS THE SWITCHES IN THE SWITCH PANEL. JUMPER WIRES ARE ONLY TO BE INSTALLED BETWEEN PIN 4 AND PIN 10 ON EACH SWITCH. FAILURE TO ADHERE TO THIS GUIDELINE MAY RESULT IN DAMAGE TO YOUR AQUA-HOT AND/OR COACH. Switch Panel Wiring AC Electric Switch...
4. Move the burner switch on the interior switch panel to the The purpose of the Fenwal card is to control the propane ON position. burner. Please note that the Aqua-Hot 250P units do not have a • Verify that 12V DC power is present at Pin 10 of the unifi...
1. Disconnect the Aqua-Hot from all electrical sources. Backing Wrench 2. Close the propane ball valve on top of the Aqua-Hot cabinet. 3. Shut off the coach propane bottle at the source. 4. Using a ⅜” socket or nut driver, remove the two nuts from the ground studs located on top of the propane burner Loosen this fi...
Page 37
Aqua-Hot cabinet. Figure 50 19. Continue to carefully remove the burner from the Aqua-Hot cabinet. Please note that wires may have become entangled in your unit complicating removal. Take care to not damage any wires or other hardware within the Aqua-Hot.
Page 39
24. Reconnect the Aqua-Hot to a propane source to check for leaks in the propane fi ttings. 25. Open the propane ball valve on the Aqua-Hot and open any propane shutoff valves present within the coach. 26. Check for propane leaks around the recently reconnected propane fi...
The mounting gaskets create a tight seal between the boiler tank and the combustion chamber, and the combustion Aqua-Hot operates on both AC and DC power. Be sure chamber and the burner mounting plate. to disconnect the 120V AC power supply from the Aqua- Hot prior to servicing.
The hot surface igniter ignites the propane gas and air mixture inside of the combustion chamber. It will activate Aqua-Hot operates on both AC and DC power. Be sure approximately 10 seconds after the initial start-up sequence to disconnect the 120V AC power supply from the Aqua- begins, and approximately fi...
Page 42
Aqua-Hot. 2. Turn off the propane at the ball valve on top of the Aqua- Hot. 3. Remove the access cover of the Aqua-Hot to gain access to internal components. 4. Disconnect the hot surface igniter from the buck boost module.
The refractory acts as an insulator to protect the hot surface igniter from being overheated by the fl ame. Troubleshoot the Aqua-Hot operates on both AC and DC power. Be sure refractory if the propane burner “pops” on ignition, or if the to disconnect the 120V AC power supply from the Aqua- propane burner fails to ignite.
Before troubleshooting the dual-stage propane gas valve, ensure that the coach has an adequate supply of propane gas, and that all valves and shutoffs are open, allowing propane fl ow to the Aqua-Hot. Replacement Procedure: 1. Shut off the propane gas supply by turning the propane Troubleshooting: inlet port ball valve to the OFF position.
Page 45
Tighten this fi tting Figure 66 Figure 64 12. Tighten the bulkhead fi tting to the Aqua-Hot cabinet. Remove the fi ttings present at the top and bottom of the dual stage propane gas valve shown below. Backing Wrench here Tighten this fi...
“back-fl ows” into the 3. Remove the defective switch. cabinet of the Aqua-Hot, or if there is an obstruction or damage to the exhaust system. 4. Secure the replacement switch to the side of the propane burner.
” Allen wrench, remove the nuts securing the 3 / 16 Replace the fan validation switch if the switch fails to operate fan validation switch to the cabinet wall of the Aqua-Hot. or if its physically damaged. 5. Remove the defective switch.
Page 52
1. Move the propane burner switch on the interior switch panel to the OFF position. If necessary, allow the propane burner to completely shut down. 2. Disconnect the Aqua-Hot from any power source. 3. Locate the buck boost module to be replaced. Reference Figure 80.
The fl ame sensor produces a small current, measured in micro-amperes (µA). This current is too small to be detected by most retail multimeter. This functionality is necessary to troubleshoot properly. Please contact Aqua-Hot Heating Systems at 574-AIR-XCEL (574-247-9235) to assist in diagnosing the fl ame sensor.
Page 54
fl ame sensor once it has been deemed to be non-functional. Replacement Procedure: 1. Disconnect the Aqua-Hot from any and all power sources. 2. Ensure that the Aqua-Hot has cooled down completely. 3. Disconnect #35 from the fl ame sensor.
Fluid Expansion Bottle Procedure: • Control Thermostat 1. Attach an external fi ll pump and hose to the Aqua-Hot • Electric Element at the ball valve located just above the three-way valve. If the interior heating loop is not purged, it may contain...
The warranty does not cover freeze damage. De-Winterization: NOTE: The Aqua-Hot can continue to be used for interior heat once the domestic hot water system has been winterized. 1. To de-winterize the unit, connect a freshwater source to the coach.
• Ensure that all coach-side hot water faucets are closed. • Tempering Valve • Locate the relay control board within the Aqua-Hot unit. See ○ Reference Page 26 to troubleshoot the tempering valve. Page 10 to identify this component. Once these components have been diagnosed, restart the •...
Page 58
A seized circulation pump contact Technical Support at 574-AIR-XCEL (574-247-9235), • Air trapped in the coach heating loop or take the coach to an Aqua-Hot Factory Authorized Service Center. One can be found at www.aquahot.com. • A malfunctioning low-temperature cutoff thermostat Stage 1: •...
This section will cover troubleshooting the propane burner if 14. Follow the instructions on Page 36 to remove the propane it becomes inoperative. burner from the Aqua-Hot. This will grant access to components for troubleshooting. If additional assistance if needed, please contact the technical support department at 574-AIR-XCEL (574-247-9235).
“boiler” type antifreeze in the concentrated propylene glycol antifreeze with water; suppliers Aqua-Hot. Propylene glycol is a safer alternative to the more of premixed antifreeze are responsible for the use of high- toxic ethylene glycol antifreeze; however, as mandated by...
Page 61
Generally Recognized As Safe (“GRAS”) by the FDA could Therefore, as water is an excellent heat conductor, it is result in serious bodily harm to damage to the Aqua-Hot added to the mixture. Propylene glycol antifreeze solution, system.
Need help?
Do you have a question about the 200 Series and is the answer not in the manual?
Questions and answers