68
  Connecting to AC
 1. Use the supplied Allen key to open the 4 screws of the auto-transformer and remove
its cover.
 2. Prepare cables and connect as described in the following table:
Recommended
cable type
(min-max AWG)
AC
8 AWG (6-20
AWG)
Grounding
10 AWG cable
Temperature Sensor
Figure 30: Connecting to the auto-transformer
StorEdge
Auto-transformer
Connection Unit
connection
3-pin terminal
block: L1
3-pin terminal
block: L2
3-pin terminal
Neutral terminal: N
block: N
Grounding Bus-
bar
connection
Line terminal: L1
Line terminal: L2
Grounding lug
StorEdge Solution with Backup MAN-01-00262-1.5
Connection method
Insert the wire into the
round opening and push
to clamp the wire.
 
 