Fitting the trap

1.
2.
Fig. 29
Danger
If the trap is not full, flue gas can escape.
Escaping flue gas can cause life threatening
carbon monoxide poisoning.
Always fill the trap with water before commis-
sioning.

Connecting the neutralising system

Fig. 30

Connections on the flue gas side

It is essential that a boiler flue connection (accesso-
ries) is used for connecting the flue outlet.
36
3.
Neutralising system installation instructions
1. Site the neutralising system either behind or adja-
cent to the boiler.
2. Trim the condensate hose supplied to the required
length. Connect the condensate hose to the trap.
Connect the condensate hose to the neutralising
system with a constant fall.
3. Connect the neutralising system to the drainage
system.
Note
Observe local waste water regulations.