ABB SACE Emax Series Installation, Service And Maintenance Instructions page 99

Low voltage air circuit-breakers
Table of Contents

Advertisement

You will be prompted to input a Password
complete the password entry procedure (par. 14.3.6)
press the ↵ key (enter)
Change the date using the keys ↓ (arrow down)
↑ (arrow up) and confirm by pressing the ↵ key (enter).
Press ESC twice to return to the Main Menu.
Procedure requiring the confirmation of any programming
For instance, to change the Curve of the Protection L, the correct sequence is as follows:
Press ESC to access the Main Menu.
From the Main Menu select the item PROTECTIONS
press the ↵ key (enter)
From the Protections Menu select the item PROTECTION L
press the ↵ key (enter)
From the Protection L Menu select the item CURVE
press the ↵ key (enter)
You will be prompted to input a Password
complete the password entry procedure (par. 14.3.6)
press the ↵ key (enter)
L2234
Model
L2778
Password
0***
Enter password
Date
January 12, 2004
Enter password
10:22:53
400 A
(I )
1
N
1/5
1/5
Menu
Menu
Protections
Protections
Measurements
Measures
Settings
Settings
Protections settings
Protections settings
1/15
Protections
L Protection
S Protection
S2 Protection
Overload
1/4
L Protection
Function
Threshold I1
Time T1
t=k/i
Password
0***
Enter password
Apparatus
Doc. No.
1SDH000460R0002
2
Scale
Emax
Page No.
98/158