14 SACE PR123/P Release - Identification

The PR123/P units available, in accordance with the IEC standards, together with the various protections and the various standard and optional
modules, are illustrated in the following figure:
Note (1): See par. 16.6
14.1
Standard
The PR123/P has been designed to work in accordance with the international standard:
IEC 60947-2 Low voltage apparatus. Circuit-breakers.
14.2

Specifications

1 4 . 2 . 1 General
The PR123/P is a high-performance self-supplied protection unit with Protection, Measurement, Data storage, Communication (optional), Self-
test, Load control and Zone selectivity functions for the ABB SACE 'Emax' range of 3- and 4-pole low-voltage air circuit-breakers. The unit's
user interface also enables parameter setup and completes the prealarm and alarm management for the protection and watchdog functions.
The protections available are:
Symbol
Protection against
L
overload with inverse long time delay
S, S2
short-circuit with adjustable delay
D
directional short-circuit with adjustable delay
I
instantaneous short-circuit
G
earth fault with adjustable delay
U
phase current unbalance
O T
temperature out of range
UV
undervoltage
OV
overvoltage
RV
residual voltage
RP
reverse active power
UF
underfrequency
O F
overfrequency
M C R
closing on short-circuit
The PR123/P can be installed on 3-pole CBs with and without an external neutral, or on 4-pole CBs.
It should be noted that the reference current for the PR123/P is the In (the rated current defined by the front Rating Plug) and not the Iu (the
uninterrupted rated current of the CB itself).
Example: the CB E1B800 with a 400A Rating Plug has an Iu of 800A and an In of 400A.
The unit opens the circuit-breaker in which it is installed by means of the TC, which takes effect directly on the device's mechanical leverism.
The protection unit is self-supplied by current sensors and primary voltages via the PR120/V module.
The unit is made using digital microprocessor technology and interfaces with the user by means of a graphic display and keyboard.
L2234
Model
L2778
PR123/P
Protections
For all versions
Optional modules available
PR120/D-M - COM
PR120/K - SIGNALLING
PR120/D-BT - WL-COM
BT030
Rc
(1)
PR123/P
2
Apparatus
Doc. No.
1SDH000460R0002
Scale
Emax
Page No.
76/158