If you select "None" for the stop event, the data logger can be stopped only by a stop command from the operator panel, from the system or following
a trip generated by the relay.
16.4.2.4

Setting and viewing customized stop events (triggers)

From the system, you can set customized stop events (triggers) to coincide with the events shown in paragraph 16.5.
In the event of a customized trigger point, the following window is displayed:
Stop event
L Prealarm
Any Trip
Custom
16.4.2.5

Setting the stopping delay

The stopping delay can be set between 0.00 [s] and 10.00 [s], in 0.01 [s] steps.
Data logger
Sampling freq.
Stop event
Stop delay
0.00 s
In the event of a trip, this data storage process is stopped after 10 ms, even if a longer stopping delay has been selected.

1 6 . 4 . 2 . 6 Restart/Stop Data Logger

Using the Restart/Stop options, you can restart or stop the recording by the data logger:
Data logger
Stop event
Stop delay
Restart
Restart
16.4.3

Recording time windows

The data logger's measurements are recorded in a time window, the duration of which is defined and synchronized by an event (trigger/stop
event) of your choice.
The following figure displays the time window, the trigger and the samples available in gray:
Samples
The user can select the sampling frequency (see par. 16.4.2.2), the type of stop event (trigger) (see par. 16.4.2.3) and the stopping delay (see
par. 16.4.2.4) so as to obtain the required pre-trigger with respect to the selected event.
Depending on the selection you make, the stopping delay may be nil, or it may be lower or higher than the recording time, as illustrated in the
following figure:
L2234
Model
L2778
5/5
None
4/6
Stop delay
Enter ↵
5/6
Data logger
Stop delay
Restart
Stop
Measurements available
Pretrigger
1/Freq
Stopping delay = 0
Stopping delay < recording time
Trigger
0.00 s
Enter password
6/6
Stop
Stopping
delay
Trigger
Recording time
Stopping delay > recording time
Trigger
Trigger
Apparatus
Doc. No.
Emax
1SDH000460R0002
Scale
Page No.
129/158