Error Messages Displayed In Pop-Up Windows - ABB SACE Emax Series Installation, Service And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

Alarm message
Configuration
Configuration
Timing UV
Timing OV
Timing RV
Timing RP
Timing UF
Timing OF

13.6.4 Error messages displayed in pop-up windows

All the messages that appear on the display in a pop-up window are described below.
Error message
Password error
Session impossible
Value outside range
Exception 6
Unavailable
Invalid date
Parameters revised
Cancelled
Failed
Failed 1001
Failed 1002
Failed 1009
Failed 3001
Failed 3002
Failed 3003
L2234
Model
L2778
Description
Parameters inconsistency
Relay key plug data inconsistency
Timing protection UV
Timing protection OV
Timing protection RV
Timing protection RP
Timing protection UF
Timing protection OF
Description
A programming session cannot be started due to a contingency (e.g. a timer-controlled delay still elapsing)
Value beyond the established limits
Command temporarily unavailable
Function temporarily unavailable
Date has not been set
Programming session concluded correctly
Programming session cancelled
Programming session rejected
Inconsistent thresholds of protections L and S
Inconsistent thresholds of protections I and S
Zone selectivity enabled in both protection S and G or Gext
Inconsistency as to language change
Inconsistency on Rc toroid
Inconsistency as to external Neutral configuration
Notes
Apparatus
Doc. No.
1SDH000460R0002
Scale
Emax
Page No.
73/158