Pr120/K Signalling Module; Characteristics Of The Digital Input; Characteristics Of The Signalling Contacts - ABB SACE Emax Series Installation, Service And Maintenance Instructions

Low voltage air circuit-breakers
Table of Contents

Advertisement

15.3

PR120/K signalling module

1 5 . 3 . 1
General characteristics
The module enables the local signalling of alarms and circuit-breaker trips.
There are two possible configurations for the SIGNALLING module:
- default configuration: 1 digital input, 3 contacts with pole in common, 1 independent contact;
- alternative configuration: 4 independent contacts. In this case, the digital input is wired, but not brought up to the terminal block.
The two configurations are alternative to each other. You can switch from one configuration to the other without changing the module, by using
a different wiring, as illustrated in the wiring diagrams in figs. 46 or 47.
15.3.2
Front view
- "Power" LED (lit when Vaux or PR120/V are installed)
- N° 4 LED: associated with the signalling contacts.
15.3.3
Releases complete with the module
- optional for PR122/P
- optional for PR123/P
15.3.4

Characteristics of the digital input

The unit enables the digital input to be associated with the following functions:
- enabling of an alternative set of parameters, set B (PR123/P only);
- outside trip control;
- zeroing release trips;
- resetting PR120/K contacts;
- local/remote enabling;
- resetting energy meters.
The digital input is activated by a 24VDC + 20% voltage.
For the load control function, the module can be used as an actuator.

15.3.5 Characteristics of the signalling contacts

The following data are defined for resistive loads (cos ϕ = 1)
Type of contact
Max switching voltage
Max switching current
Max switching power
Breaking capacity at 35
VDC
Breaking capacity at 120 VDC
Breaking capacity at 250 VAC
Breaking capacity at 380 VAC
Contact/coil insulation
Contact/contact insulation
L2234
Model
L2778
SPST
130 VDC
380 VAC
5 A
8 A
175 W
2000 VA
5 A
----
0.2 A
----
----
8 A
----
5.2 A
4000 Veff
1000 Veff
Apparatus
Doc. No.
1SDH000460R0002
Scale
Emax
Page No.
121/158