Liebert® NXL™ System Control Cabinet, SCCi Installation Manual — 1600A-5000A, 60Hz, Three-Phase...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
ASC. Observez également toutes les précautions décrites dans le manuel d’utilisation et d’entretien, SL-25414, avant et pendant toutes les procédures d’entretien. Observez toutes les précautions de sécurité appropriées lorsque vous travaillez sur à proximité d’une source c.c. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Page 6
One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Page 7
Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Before installing the Liebert NXL SCCi, please carry out the following preliminary checks: • Examine the Liebert NXL SCCi for transit damage, both internally and externally. Report any damage to the shipper immediately. • Verify that the correct equipment is being installed. The Liebert NXL SCCi cabinet has an identification tag on the interior doors listing the type, size and main calibration parameters of the UPS.
2. Attach the support channel to the left and right sides using the hardware shown in Detail C in Figure 2. Attach the front brace to the left and right sides with the hardware shown in Detail H in Figure 2. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Page 10
11. Rack out the static switch. After the static switch has been disengaged, move it forward to the front of the static switch table support. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Page 11
Detail E switch is free to roll Detail D Leveler onto the static switch Detail B Step 7 Detail C Step 8 Step 9 support table. Step 10 ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
EXTERNA L INT BATT STATUS BYP CNTL TB0825 TB0812 TB0817 RECT REPO CNTL BATT MTR TB1156 LBS VO LTAGE TB0818 TB0820 TB0826 REPO TB0824 CNTRLN STATUS FORM C ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
REPO Switch, common contact Key status switch, closed = key removed TB082 14AWG/500ft. Key Status Input Form C Key status switch, common (150m) Key status switch, closed = key inserted ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
P3103 on the Inter-Module Communication (IMC) board (refer to 3.0 - Installation Drawings). Table 4 Parallel from SCC module Inter-Module Communication Board to other Inter-Module Communication Board in system Terminal Designation Wire Size/ Maximum From Signal Name Length Primary Connections ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Page 15
Care must be taken so drain wire does not touch any other component in module. 8. Attach control wires to side of control door where Inter-Module Board (IMC) is attached. Do not run wires across IMC board. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
For systems that use Remote Input Breakers (RIB), the controls for the Aux contacts, UVR, Motor Operator (optional) and voltage sense will go between the Remote breaker and the SCC Input I/O section. See Figure 6. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Circuit Breaker) that are required to be used in UL-listed switchgear or switchboards. The circuit breaker must have a short-time rating not exceeding 480 volts at 150K amperes, for 5 cycles. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Press Internal Option Settings from the Config menu. 2. Press the Input Contact Isolator that is to be configured. The Input Contact Isolator dialog box is displayed. Figure 9 Input contact isolator dialog box ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
Control wiring runs should not be combined in the same conduit. Signal voltage: 100mA @ 12VDC. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable. ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...
If a smaller input feed breaker is used, the input current limit can be adjusted. Contact your Vertiv representative for more information. The Rectifier Input Feed Breaker must be set to handle the Liebert NXL transformer inrush of up to eight times the nominal current.
Page 30
Notes ® ™ ™ Vertiv | Liebert System Control Cabinet Installation Manual |...