Viessmann Vitocrossal 200 Series Service Instructions Manual page 37

Table of Contents

Advertisement

Burner control unit VUC 310
Configurations:
Menu
Description
point
5
Changeover from the operating display of
the burner control unit phase to other proc-
ess information
6
Configuration of control function operating
parameters
Menu point "5" is used to display the following process information:
Sub-menu point
Process information
0
Phase
1
Boiler water temperature
2
Flue gas temperature
3
Ionisation current
4
Set speed
5
PWM variable
6
Actual speed
7
Gas pressure switch 1
8
Gas pressure switch 2
9
Air pressure switch LDW1
A
Gas valve 1
B
Gas valve 2
Display ionisation current example. Press the following
keys:
1. S longer than 2 s, " " flashes.
2.
until "5" is shown under Service.
Menu point "6" is used to change the following operating parameters:
Sub-menu
Parameter
point
1
Maximum operational output
2
Gas type
4
Max. boiler water temperature
5
Boiler controller integral threshold (effec-
tive with integral method, do not adjust)
6
Boiler controller runtime optimization (do
not adjust)
7
Motorised flue gas damper
8
Characteristics with gas pressure too
low
Not available for all boiler types.
*1
(cont.)
*1
*1
3. S "5" is displayed under Status.
4.
5. S "3" is shown under Status; under Service the ion-
Setting range/unit
% of rated heating out-
put
0 = Natural gas
1 = LPG
5 to 127 °C
1 to 255 K x min
0 = Minimum pause
1 = integral method
0 = without flue gas
1 = with flue gas
0 = interlocked
1 = blocked
Unit/scale
1
30
°C
°C
I in 1/10
μ
%
%
n in 10/min
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
until "3" is shown under Service.
isation current is shown during operation (e.g.
30 = 3.0
A).
µ
Delivered condition
100 %
0
*1
101 °C
30 K x min
1
0
damper
damper
1
Burner control unit
A
37