Fault codes
(cont.)
Fault code dis-
System characteristics
played
F EB
Burner blocked
F EC
Burner control unit in a fault
state
F ED
Burner control unit in a fault
state
F F1
Burner control unit in a fault
state; system cools down.
F F2
Burner control unit in a fault
state; system cools down.
F FB
Burner does not start
Internal system faults
Internal system faults will be shown if the correct pro-
gram sequence can no longer be guaranteed.
Displayed fault
System characteristics
code
F E5, F EC,
Fault in burner control unit
F ED, F FF
area
F FD
Fault in burner control unit
area
Cause
Burner not enabled via ex-
ternal contact.
Internal error in feedback
from safety relay.
Internal error in feedback
from ignition relay.
Flue gas temperature lim-
iter has responded
Flue gas temperature
too high
Excessive gas through-
put
Boiler water temperature
limiter has responded.
Boiler water temperature
too high.
Combustion chamber
pressure too high
(LDW2)
Condensate backed up
Flue gas path blocked
Flue gas flap does not
open or close
Burner control unit con-
figured incorrectly
Cause
Internal system fault and
EMC
See the following table
Troubleshooting
Measures
Check components connected to
TR/TR EIN at plug
of the
aBÖ
Vitotronic.
Reset the burner control unit. Re-
place burner control unit if re-
quired.
Reset the burner control unit. Re-
place burner control unit if re-
quired.
Wait until temperature falls below
the permissible flue gas tempera-
ture.
Check the system pressure.
Check heat exchanger surfaces
for soiling.
Reset burner control unit.
Check the CO
setting.
2
Adjust gas throughput in accord-
ance with the rated boiler heating
output. See "Specification" for
connected values.
Wait until temperature falls below
the permissible boiler water tem-
perature.
Reset burner control unit.
Check condensate drain and flue
gas path for blockages.
Check flue gas damper.
Check motorised flue gas damp-
er operating parameters.
Measures
Reset burner control unit. Replace
the burner control unit if the fault
persists.
See the following table
45