Viessmann Vitocrossal 200 Series Service Instructions Manual page 17

Table of Contents

Advertisement

Checking the CO
Relationship between CO
Gas type
Wobbe index
kWh/m
3
Natural gas
16.10
E
15.00
14.00
13.00
12.00
Permissible CO
content (depending on the Wobbe index of the gas type)
2
Gas type
CO
con-
2
tent
at
Natural gas
upper heat-
E
ing output
(100 %)
lower heat-
ing output
(0 %)
Natural gas
upper heat-
H
ing output
(100 %)
lower heat-
ing output
(0 %)
Natural gas
upper heat-
LL
ing output
(100 %)
lower heat-
ing output
(0 %)
Natural gas
upper heat-
L
ing output
(100 %)
lower heat-
ing output
(0 %)
LPG P
upper heat-
ing output
(100 %)
lower heat-
ing output
(0 %)
content
(cont.)
2
value and Wobbe index
2
CO
setting
2
%
MJ/m
3
58.00
11.0
54.00
9.7
50.40
8.9
46.80
8.2
43.20
7.4
75 and 87
115
7.1 - 10.2 % 7.0 - 10.1 % 7.0 - 10.1 % 7.1 - 10.2 % 7.1 - 10.2 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
8.0 - 10.2 % 7.9 - 10.1 % 7.9 - 10.1 % 8.0 - 10.2 % 8.0 - 10.2 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
7.2 - 10.0 %
7.1 - 9.9 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
8.3 - 10.0 %
8.2 - 9.9 %
Actual value at upper heating output minus
0.3 - 0.7 %
0.3 - 0.7 %
Actual value at upper heating output minus
Commissioning, inspection, maintenance
Rated heating output in kW
142
0.3 - 0.7 %
0.4 - 0.8 %
0.3 - 0.7 %
0.4 - 0.8 %
7.1 - 9.9 % 7.2 - 10.0 % 7.2 - 10.0 %
0.3 - 0.7 %
0.4 - 0.8 %
8.2 - 9.9 % 8.3 - 10.0 % 8.3 - 10.0 %
0.3 - 0.7 %
0.4 - 0.8 %
9.6 - 11.6 % 9.6 - 11.6 %
1.0 - 2.0 %
186
246
7.1 - 10.2 %
0.7 - 1.0 %
0.4 - 0.8 %
8.0 - 10.2 %
0.7 - 1.0 %
0.4 - 0.8 %
7.2 - 10.0 %
0.7 - 1.0 %
0.4 - 0.8 %
8.3 - 10.0 %
0.7 - 1.0 %
0.4 - 0.8 %
9.6 - 11.6 %
1.0 - 2.0 %
1.0 - 2.0 %
311
17