Checking static pressure and supply pressure

Static pressure
Rated heating output 75 and 87 kW
Fig. 7
Supply pressure
Note
See type plate for supply pressures for operation with
other country-specific gas types.
1. Start the burner with emissions test mode enabled
(in control unit menu).
A
Commissioning, inspection, maintenance
Rated heating output 115 to 311 kW
A
Fig. 8
1. Close the gas shut-off valve.
2. Undo the screw in test connector
remove.
3. Connect the pressure tester at test connector
4. Open the gas shut-off valve.
5. Check the static pressure.
6. Record the actual value in the report (on
page 55).